Refrigerant · HFO/HFC blend

R-450A pressure-temperature chart and data

R-134a / R-1234ze(E). Safety class A1, GWP 604. Lower-GWP replacement for R-134a.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-450A data sheet

Made ofR-134a 42 / R-1234ze(E) 58 (mass %)
TypeHFO/HFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)604
Boils at 1 atm-10.5 °F (-23.6 °C)
Critical temperature221.7 °F (105.4 °C)
Temperature glideabout 1.1 °F
Low side at 5 °F evaporating6.1 psig (42 kPa)
High side at 86 °F condensing85.1 psig (587 kPa)
Old cylinder colourSapphire blue
OilPOE
Used forLower-GWP replacement for R-134a.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-450A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 22.8V 22.6-77-77
-59-50.6V 22.6V 22.4-77-76
-58-50.0V 22.4V 22.1-76-75
-57-49.4V 22.1V 21.9-75-74
-56-48.9V 21.9V 21.6-74-73
-55-48.3V 21.6V 21.3-73-72
-54-47.8V 21.3V 21.1-72-71
-53-47.2V 21.1V 20.8-71-70
-52-46.7V 20.8V 20.5-70-69
-51-46.1V 20.5V 20.2-69-68
-50-45.6V 20.2V 19.9-68-67
-49-45.0V 19.9V 19.6-67-66
-48-44.4V 19.6V 19.2-66-65
-47-43.9V 19.2V 18.9-65-64
-46-43.3V 18.9V 18.6-64-63
-45-42.8V 18.6V 18.2-63-62
-44-42.2V 18.2V 17.9-62-61
-43-41.7V 17.9V 17.5-61-59
-42-41.1V 17.5V 17.1-59-58
-41-40.6V 17.1V 16.8-58-57
-40-40.0V 16.8V 16.4-57-55
-39-39.4V 16.4V 16.0-55-54
-38-38.9V 16.0V 15.6-54-53
-37-38.3V 15.6V 15.1-53-51
-36-37.8V 15.1V 14.7-51-50
-35-37.2V 14.7V 14.3-50-48
-34-36.7V 14.3V 13.8-48-47
-33-36.1V 13.8V 13.4-47-45
-32-35.6V 13.4V 12.9-45-44
-31-35.0V 12.9V 12.4-44-42
-30-34.4V 12.4V 11.9-42-40
-29-33.9V 12.0V 11.4-40-39
-28-33.3V 11.4V 10.9-39-37
-27-32.8V 10.9V 10.4-37-35
-26-32.2V 10.4V 9.9-35-33
-25-31.7V 9.9V 9.3-33-32
-24-31.1V 9.3V 8.8-32-30
-23-30.6V 8.8V 8.2-30-28
-22-30.0V 8.2V 7.6-28-26
-21-29.4V 7.6V 7.0-26-24
-20-28.9V 7.0V 6.4-24-22
-19-28.3V 6.4V 5.8-22-20
-18-27.8V 5.8V 5.2-20-17
-17-27.2V 5.2V 4.5-18-15
-16-26.7V 4.5V 3.8-15-13
-15-26.1V 3.9V 3.2-13-11
-14-25.6V 3.2V 2.5-11-8
-13-25.0V 2.5V 1.8-9-6
-12-24.4V 1.8V 1.1-6-4
-11-23.9V 1.1V 0.3-4-1
-10-23.3V 0.40.2-11
-9-22.80.20.614
-8-22.20.60.947
-7-21.70.91.369
-6-21.11.31.7912
-5-20.61.72.11215
-4-20.02.12.51518
-3-19.42.53.01720
-2-18.92.93.42023
-1-18.33.43.82326
0-17.83.84.32629
1-17.24.24.72932
2-16.74.75.23236
3-16.15.15.63539
4-15.65.66.13942
5-15.06.16.64245
6-14.46.57.14549
7-13.97.07.64952
8-13.37.58.15256
9-12.88.18.65659
10-12.28.69.15963
11-11.79.19.76367
12-11.19.610.26670
13-10.610.210.87074
14-10.010.711.37478
15-9.411.311.97882
16-8.911.912.58286
17-8.312.413.18690
18-7.813.113.79094
19-7.213.714.39499
20-6.714.314.998103
21-6.114.915.6103107
22-5.615.516.2107112
23-5.016.216.9111116
24-4.416.817.6116121
25-3.917.518.2121126
26-3.318.218.9125130
27-2.818.919.6130135
28-2.219.620.3135140
29-1.720.321.1140145
30-1.121.021.8145150
31-0.621.722.5150155
320.022.523.3155161
330.623.224.1160166
341.124.024.9165171
351.724.825.6171177
362.225.626.4176182
372.826.427.3182188
383.327.228.1187194
393.928.028.9193200
404.428.929.8199205
415.029.730.7205211
425.630.631.6211218
436.131.432.4217224
446.732.433.4223230
457.233.334.3229236
467.834.235.2236243
478.335.136.1242249
488.936.037.1249256
499.437.038.1255263
5010.038.039.1262269
5110.639.040.1269276
5211.140.041.1276283
5311.741.042.1283291
5412.242.043.2290298
5512.843.144.2297305
5613.344.145.3304312
5713.945.246.4312320
5814.446.347.5319328
5915.047.448.6327335
6015.648.549.8334343
6116.149.650.9342351
6216.750.852.1350359
6317.252.053.3358367
6417.853.154.5366376
6518.354.355.7375384
6618.955.556.9383392
6719.456.858.2391401
6820.058.059.4400410
6920.659.360.7409419
7021.160.662.0418427
7121.761.963.3427437
7222.263.264.7436446
7322.864.566.0445455
7423.365.867.4454464
7523.967.268.7463474
7624.468.670.1473484
7725.070.071.5482493
7825.671.473.0492503
7926.172.874.4502513
8026.774.375.9512523
8127.275.877.4522534
8227.877.278.9532544
8328.378.780.4543555
8428.980.382.0553565
8529.481.883.5564576
8630.083.485.1575587
8730.685.086.7586598
8831.186.588.3597609
8931.788.290.0608620
9032.289.891.6619632
9132.891.593.3631643
9233.393.195.0642655
9333.994.896.7654667
9434.496.598.5666679
9535.098.3100678691
9635.6100102690703
9736.1102104702716
9836.7104106714728
9937.2105107727741
10037.8107109740754
10138.3109111752767
10238.9111113766780
10339.4113115779793
10440.0115117792807
10540.6117119805820
10641.1119121819834
10741.7121123833848
10842.2123125847862
10942.8125127861876
11043.3127129875890
11143.9129131889905
11244.4131133904919
11345.0133136918934
11445.6135138933949
11546.1138140948964
11646.7140142963980
11747.2142144979995
11847.81441479941011
11948.314614910101027
12048.914915110261042
12149.415115410421059
12250.015315610581075
12350.615615810741091
12451.115816110901108
12551.716116311071125
12652.216316611241142
12752.816516811411159
12853.316817111581176
12953.917117311761194
13054.417317611931212

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-450A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 22.83.5-77240.24V 22.6
-55-48.3V 21.64.1-73280.28V 21.3
-50-45.6V 20.24.8-68330.33V 19.9
-45-42.8V 18.65.6-63380.38V 18.2
-40-40.0V 16.86.5-57450.45V 16.4
-35-37.2V 14.77.5-50510.51V 14.3
-30-34.4V 12.48.6-42590.59V 11.9
-25-31.7V 9.99.8-33680.68V 9.3
-20-28.9V 7.011.2-24780.78V 6.4
-15-26.1V 3.912.8-13880.88V 3.2
-10-23.3V 0.414.5-11001.000.2
-5-20.61.716.4121131.132.1
0-17.83.818.5261271.274.3
5-15.06.120.8421431.436.6
10-12.28.623.3591601.609.1
15-9.411.326.0781791.7911.9
20-6.714.329.0982002.0014.9
25-3.917.532.21212222.2218.2
30-1.121.035.71452462.4621.8
351.724.839.51712722.7225.6
404.428.943.51993003.0029.8
457.233.347.92293313.3134.3
5010.038.052.72623633.6339.1
5512.843.157.82973983.9844.2
6015.648.563.23344364.3649.8
6518.354.369.03754764.7655.7
7021.160.675.34185195.1962.0
7523.967.281.94635655.6568.7
8026.774.389.05126136.1375.9
8529.481.896.55646656.6583.5
9032.289.8104.56197207.2091.6
9535.098.3113.06787797.79100
10037.8107122.07408418.41109
10540.6117131.58059079.07119
11043.3127141.68759769.76129
11546.1138152.2948104910.49140
12048.9149163.41026112711.27151
12551.7161175.31107120812.08163
13054.4173187.71193129412.94176

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.