Refrigerant · HFO/HFC blend

R-448A pressure-temperature chart and data

R-32 / R-125 / R-134a / R-1234ze(E) / R-1234yf. Safety class A1, GWP 1,387. Lower-GWP replacement for R-404A and R-507A in commercial refrigeration.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-448A data sheet

Made ofR-32 26 / R-125 26 / R-134a 21 / R-1234ze(E) 7 / R-1234yf 20 (mass %)
TypeHFO/HFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)1,387
Boils at 1 atm-51.1 °F (-46.2 °C)
Critical temperature181 °F (82.8 °C)
Temperature glideabout 11.1 °F
Low side at 5 °F evaporating28.3 psig (195 kPa)
High side at 86 °F condensing199 psig (1369 kPa)
Old cylinder colourGentian blue
OilPOE
Used forLower-GWP replacement for R-404A and R-507A in commercial refrigeration.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-448A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 13.4V 6.5-45-22
-59-50.6V 12.9V 5.8-44-20
-58-50.0V 12.4V 5.2-42-17
-57-49.4V 11.8V 4.4-40-15
-56-48.9V 11.3V 3.7-38-13
-55-48.3V 10.7V 3.0-36-10
-54-47.8V 10.1V 2.2-34-8
-53-47.2V 9.5V 1.5-32-5
-52-46.7V 8.9V 0.7-30-2
-51-46.1V 8.30.1-280
-50-45.6V 7.70.5-263
-49-45.0V 7.00.9-246
-48-44.4V 6.41.3-229
-47-43.9V 5.71.7-1912
-46-43.3V 5.02.1-1715
-45-42.8V 4.32.6-1518
-44-42.2V 3.63.0-1221
-43-41.7V 2.83.5-1024
-42-41.1V 2.14.0-727
-41-40.6V 1.34.5-431
-40-40.0V 0.55.0-234
-39-39.40.25.5138
-38-38.90.66.0441
-37-38.31.06.5745
-36-37.81.47.01048
-35-37.21.87.61352
-34-36.72.38.11656
-33-36.12.78.71960
-32-35.63.29.32264
-31-35.03.79.92568
-30-34.44.210.52972
-29-33.94.711.13276
-28-33.35.211.73681
-27-32.85.712.33985
-26-32.26.213.04389
-25-31.76.713.64694
-24-31.17.314.35099
-23-30.67.815.054103
-22-30.08.415.758108
-21-29.48.916.462113
-20-28.99.517.166118
-19-28.310.117.870123
-18-27.810.718.674128
-17-27.211.419.378133
-16-26.712.020.183139
-15-26.112.620.987144
-14-25.613.321.792149
-13-25.014.022.596155
-12-24.414.723.3101161
-11-23.915.324.1106166
-10-23.316.125.0111172
-9-22.816.825.9116178
-8-22.217.526.7121184
-7-21.718.227.6126191
-6-21.119.028.6131197
-5-20.619.829.5136203
-4-20.020.630.4142210
-3-19.421.431.4147216
-2-18.922.232.3153223
-1-18.323.033.3159230
0-17.823.834.3164237
1-17.224.735.4170244
2-16.725.636.4176251
3-16.126.437.4182258
4-15.627.438.5189265
5-15.028.339.6195273
6-14.429.240.7201280
7-13.930.141.8208288
8-13.331.142.9214296
9-12.832.144.1221304
10-12.233.145.3228312
11-11.734.146.4235320
12-11.135.147.6242328
13-10.636.248.9249337
14-10.037.250.1257345
15-9.438.351.4264354
16-8.939.452.6272363
17-8.340.553.9279372
18-7.841.655.3287381
19-7.242.856.6295390
20-6.743.957.9303399
21-6.145.159.3311409
22-5.646.360.7319419
23-5.047.562.1328428
24-4.448.863.5336438
25-3.950.065.0345448
26-3.351.366.5354458
27-2.852.668.0363468
28-2.253.969.5372479
29-1.755.371.0381489
30-1.156.672.5390500
31-0.658.074.1400511
320.059.475.7409522
330.660.877.3419533
341.162.279.0429544
351.763.780.6439556
362.265.182.3449568
372.866.684.0459579
383.368.285.7470591
393.969.787.5480603
404.471.289.3491615
415.072.891.0502628
425.674.492.9513640
436.176.094.7524653
446.777.796.6536666
457.279.498.5547679
467.881.1100559692
478.382.8102571705
488.984.5104583719
499.486.3106595733
5010.088.1108607746
5110.689.9110620760
5211.191.7112632775
5311.793.6114645789
5412.295.5117658803
5512.897.4119671818
5613.399.3121685833
5713.9101123698848
5814.4103125712863
5915.0105127726879
6015.6107130740894
6116.1109132754910
6216.7111134768926
6317.2114137783942
6417.8116139798959
6518.3118141813975
6618.9120144828992
6719.41221468431009
6820.01251498591026
6920.61271518741043
7021.11291548901061
7121.71311569061078
7222.21341599231096
7322.81361629391114
7423.31391649561133
7523.91411679731151
7624.41441709901170
7725.014617210071189
7825.614917510241208
7926.115117810421227
8026.715418110601247
8127.215618410781266
8227.815918710971286
8328.316219011151307
8428.916419211341327
8529.416719511531348
8630.017019811721368
8730.617320211921389
8831.117620512111411
8931.717920812311432
9032.218221112511454
9132.818421412721476
9233.318721712921498
9333.919022013131520
9434.419422413341543
9535.019722713561566
9635.620023013771589
9736.120323413991612
9836.720623714211636
9937.220924114431659
10037.821324414661683
10138.321624814891708
10238.921925115121732
10339.422325515351757
10440.022625815591782
10540.623026215821807
10641.123326616061832
10741.723727016311858
10842.224027316551884
10942.824427716801910
11043.324728117051937
11143.925128517311963
11244.425528917571990
11345.025929317832018
11445.626229718092045
11546.126630118352073
11646.727030518622101
11747.227430918892129
11847.827831319172158
11948.328231719442187
12048.928632119722216
12149.429032620012245
12250.029433020292275
12350.629933420582305
12451.130333920872335
12551.730734321172365
12652.231134721472396
12752.831635221772427
12853.332035722072458
12953.932536122382490
13054.432936622692521

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-448A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 13.48.1-45560.56V 6.5
-55-48.3V 10.79.4-36650.65V 3.0
-50-45.6V 7.710.9-26750.750.5
-45-42.8V 4.312.6-15870.872.6
-40-40.0V 0.514.5-21001.005.0
-35-37.21.816.5131141.147.6
-30-34.44.218.8291301.3010.5
-25-31.76.721.4461481.4813.6
-20-28.99.524.2661671.6717.1
-15-26.112.627.3871881.8820.9
-10-23.316.130.71112122.1225.0
-5-20.619.834.51362382.3829.5
0-17.823.838.51642662.6634.3
5-15.028.343.01952962.9639.6
10-12.233.147.82283293.2945.3
15-9.438.353.02643653.6551.4
20-6.743.958.63034044.0457.9
25-3.950.064.73454464.4665.0
30-1.156.671.33904924.9272.5
351.763.778.44395405.4080.6
404.471.285.94915935.9389.3
457.279.494.15476496.4998.5
5010.088.1102.86077097.09108
5512.897.4112.16717737.73119
6015.6107122.07408418.41130
6518.3118132.58139149.14141
7021.1129143.88909919.91154
7523.9141155.8973107410.74167
8026.7154168.51060116111.61181
8529.4167181.91153125412.54195
9032.2182196.21251135313.53211
9535.0197211.31356145714.57227
10037.8213227.31466156715.67244
10540.6230244.21582168416.84262
11043.3247262.11705180718.07281
11546.1266280.91835193719.37301
12048.9286300.81972207420.74321
12551.7307321.72117221822.18343
13054.4329343.82269237123.71366

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.