Refrigerant · HFC blend

R-404A pressure-temperature chart and data

R-125 / R-143a / R-134a. Safety class A1, GWP 3,922. Low and medium-temperature commercial refrigeration. Replaced R-502 and R-22. High GWP, being phased down; replacements include R-448A, R-449A, R-407F, R-454C.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-404A data sheet

Made ofR-125 44 / R-143a 52 / R-134a 4 (mass %)
TypeHFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)3,922
Boils at 1 atm-51.2 °F (-46.2 °C)
Critical temperature161.8 °F (72.1 °C)
Temperature glideabout 1 °F
Low side at 5 °F evaporating37.7 psig (260 kPa)
High side at 86 °F condensing193 psig (1327 kPa)
Old cylinder colourOrange
OilPOE
Used forLow and medium-temperature commercial refrigeration. Replaced R-502 and R-22. High GWP, being phased down; replacements include R-448A, R-449A, R-407F, R-454C.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-404A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 7.3V 6.4-25-22
-59-50.6V 6.7V 5.7-23-19
-58-50.0V 6.0V 5.0-20-17
-57-49.4V 5.3V 4.4-18-15
-56-48.9V 4.6V 3.6-16-12
-55-48.3V 3.9V 2.9-13-10
-54-47.8V 3.2V 2.2-11-7
-53-47.2V 2.4V 1.4-8-5
-52-46.7V 1.7V 0.6-6-2
-51-46.1V 0.90.1-31
-50-45.6V 0.10.5-03
-49-45.00.30.926
-48-44.40.71.359
-47-43.91.21.7812
-46-43.31.62.11115
-45-42.82.02.61418
-44-42.22.53.01721
-43-41.72.93.52024
-42-41.13.44.02327
-41-40.63.84.42631
-40-40.04.34.93034
-39-39.44.85.43337
-38-38.95.35.93641
-37-38.35.86.44044
-36-37.86.37.04348
-35-37.26.87.54752
-34-36.77.48.15156
-33-36.17.98.65559
-32-35.68.59.25863
-31-35.09.09.86267
-30-34.49.610.36671
-29-33.910.210.97075
-28-33.310.811.57480
-27-32.811.412.27984
-26-32.212.012.88388
-25-31.712.713.48793
-24-31.113.314.19297
-23-30.614.014.896102
-22-30.014.615.4101106
-21-29.415.316.1106111
-20-28.916.016.8110116
-19-28.316.717.6115121
-18-27.817.418.3120126
-17-27.218.219.0125131
-16-26.718.919.8130136
-15-26.119.620.5135142
-14-25.620.421.3141147
-13-25.021.222.1146152
-12-24.422.022.9152158
-11-23.922.823.7157164
-10-23.323.624.6163169
-9-22.824.525.4169175
-8-22.225.326.3175181
-7-21.726.227.1180187
-6-21.127.128.0187193
-5-20.627.928.9193199
-4-20.028.829.9199206
-3-19.429.830.8205212
-2-18.930.731.7212219
-1-18.331.632.7218225
0-17.832.633.7225232
1-17.233.634.6232239
2-16.734.635.7238246
3-16.135.636.7245253
4-15.636.637.7252260
5-15.037.738.8260267
6-14.438.739.8267275
7-13.939.840.9274282
8-13.340.942.0282290
9-12.842.043.1290298
10-12.243.144.3297305
11-11.744.345.4305313
12-11.145.446.6313321
13-10.646.647.8321330
14-10.047.849.0329338
15-9.449.050.2338346
16-8.950.251.5346355
17-8.351.552.7355363
18-7.852.754.0363372
19-7.254.055.3372381
20-6.755.356.6381390
21-6.156.657.9390399
22-5.658.059.3400409
23-5.059.360.6409418
24-4.460.762.0418428
25-3.962.163.4428437
26-3.363.564.8438447
27-2.864.966.3448457
28-2.266.467.8458467
29-1.767.869.2468477
30-1.169.370.7478488
31-0.670.872.3488498
320.072.473.8499509
330.673.975.4510520
341.175.577.0521531
351.777.178.6532542
362.278.780.2543553
372.880.381.8554564
383.382.083.5565576
393.983.785.2577587
404.485.486.9589599
415.087.188.6601611
425.688.890.4613623
436.190.692.2625635
446.792.494.0637648
457.294.295.8650661
467.896.097.7662673
478.397.999.5675686
488.999.8101688699
499.4102103701712
5010.0104105714726
5110.6106107728739
5211.1108109742753
5311.7110111755767
5412.2112113769781
5512.8114115783795
5613.3116117798810
5713.9118120812824
5814.4120122827839
5915.0122124842854
6015.6124126857869
6116.1126128872884
6216.7129130887899
6317.2131133903915
6417.8133135918931
6518.3136137934947
6618.9138140950963
6719.4140142967979
6820.0143144983996
6920.614514710001013
7021.114714910171029
7121.715015210341047
7222.215215410511064
7322.815515710681081
7423.315715910861099
7523.916016211041117
7624.416316511221135
7725.016516711401153
7825.616817011581172
7926.117117311771190
8026.717317511961209
8127.217617812151228
8227.817918112341248
8328.318218412531267
8428.918518712731287
8529.418819012931307
8630.019019213131327
8730.619319513331347
8831.119619813541368
8931.719920113751389
9032.220220413961410
9132.820520814171431
9233.320921114381452
9333.921221414601474
9434.421521714821496
9535.021822015041518
9635.622122315261541
9736.122522715491563
9836.722823015711586
9937.223123315951609
10037.823523716181632
10138.323824016411656
10238.924224416651680
10339.424524716891704
10440.024925117131728
10540.625225417381753
10641.125625817631777
10741.725926117881802
10842.226326518131828
10942.826726918381853
11043.327027318641879
11143.927427618901905
11244.427828019161931
11345.028228419431958
11445.628628819701985
11546.129029219972012
11646.729429620242039
11747.229830020522067
11847.830230420802095
11948.330630821082123
12048.931031221372152
12149.431431621652180
12250.031832021942209
12350.632332522242239
12451.132732922532268
12551.733133322832298
12652.233633823132328
12752.834034223442359
12853.334434723752390
12953.934935124062421
13054.435435624372452

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-404A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 7.311.1-25770.77V 6.4
-55-48.3V 3.912.8-13880.88V 2.9
-50-45.6V 0.114.6-01011.010.5
-45-42.82.016.7141151.152.6
-40-40.04.319.0301311.314.9
-35-37.26.821.5471481.487.5
-30-34.49.624.3661681.6810.3
-25-31.712.727.4871891.8913.4
-20-28.916.030.71102122.1216.8
-15-26.119.634.31352372.3720.5
-10-23.323.638.31632642.6424.6
-5-20.627.942.61932942.9428.9
0-17.832.647.32253263.2633.7
5-15.037.752.42603613.6138.8
10-12.243.157.82973993.9944.3
15-9.449.063.73384394.3950.2
20-6.755.370.03814834.8356.6
25-3.962.176.84285295.2963.4
30-1.169.384.04785795.7970.7
351.777.191.85326336.3378.6
404.485.4100.15896906.9086.9
457.294.2108.96507517.5195.8
5010.0104118.37148168.16105
5512.8114128.37838858.85115
6015.6124138.98579589.58126
6518.3136150.2934103610.36137
7021.1147162.11017111811.18149
7523.9160174.81104120512.05162
8026.7173188.11196129712.97175
8529.4188202.21293139413.94190
9032.2202217.11396149714.97204
9535.0218232.81504160516.05220
10037.8235249.31618171917.19237
10540.6252266.71738183918.39254
11043.3270285.11864196519.65273
11546.1290304.31997209820.98292
12048.9310324.62137223822.38312
12551.7331345.92283238523.85333
13054.4354368.22437253925.39356

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.