Refrigerant · Natural (hydrocarbon)

R-1270 pressure-temperature chart and data

Propylene. Safety class A3, GWP 2. Commercial and industrial refrigeration. Highly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-1270 data sheet

NamePropylene
TypeNatural (hydrocarbon)
Safety classA3 — lower toxicity, highly flammable
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)2
Boils at 1 atm-53.7 °F (-47.6 °C)
Critical temperature195.9 °F (91.1 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating38.0 psig (262 kPa)
High side at 86 °F condensing175 psig (1204 kPa)
Old cylinder colournone assigned
OilMineral / POE
Used forCommercial and industrial refrigeration. Highly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-1270 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 4.5-15
-59-50.6V 3.8-13
-58-50.0V 3.1-11
-57-49.4V 2.4-8
-56-48.9V 1.7-6
-55-48.3V 1.0-3
-54-47.8V 0.2-1
-53-47.20.32
-52-46.70.74
-51-46.11.07
-50-45.61.410
-49-45.01.813
-48-44.42.215
-47-43.92.718
-46-43.33.121
-45-42.83.524
-44-42.24.027
-43-41.74.430
-42-41.14.934
-41-40.65.337
-40-40.05.840
-39-39.46.344
-38-38.96.847
-37-38.37.350
-36-37.87.854
-35-37.28.358
-34-36.78.961
-33-36.19.465
-32-35.610.069
-31-35.010.573
-30-34.411.176
-29-33.911.780
-28-33.312.384
-27-32.812.889
-26-32.213.593
-25-31.714.197
-24-31.114.7101
-23-30.615.3106
-22-30.016.0110
-21-29.416.7115
-20-28.917.3119
-19-28.318.0124
-18-27.818.7129
-17-27.219.4134
-16-26.720.1139
-15-26.120.9144
-14-25.621.6149
-13-25.022.3154
-12-24.423.1159
-11-23.923.9165
-10-23.324.7170
-9-22.825.5176
-8-22.226.3181
-7-21.727.1187
-6-21.127.9193
-5-20.628.8198
-4-20.029.6204
-3-19.430.5210
-2-18.931.4216
-1-18.332.3223
0-17.833.2229
1-17.234.1235
2-16.735.1242
3-16.136.0248
4-15.637.0255
5-15.038.0262
6-14.439.0269
7-13.940.0275
8-13.341.0282
9-12.842.0290
10-12.243.1297
11-11.744.1304
12-11.145.2312
13-10.646.3319
14-10.047.4327
15-9.448.5335
16-8.949.7342
17-8.350.8350
18-7.852.0358
19-7.253.2367
20-6.754.4375
21-6.155.6383
22-5.656.8392
23-5.058.1400
24-4.459.3409
25-3.960.6418
26-3.361.9427
27-2.863.2436
28-2.264.5445
29-1.765.9454
30-1.167.2464
31-0.668.6473
320.070.0483
330.671.4492
341.172.9502
351.774.3512
362.275.8522
372.877.3533
383.378.8543
393.980.3554
404.481.8564
415.083.4575
425.685.0586
436.186.5597
446.788.2608
457.289.8619
467.891.4630
478.393.1642
488.994.8654
499.496.5665
5010.098.2677
5110.6100.0689
5211.1102701
5311.7104714
5412.2105726
5512.8107739
5613.3109752
5713.9111764
5814.4113778
5915.0115791
6015.6117804
6116.1119817
6216.7121831
6317.2123845
6417.8125859
6518.3127873
6618.9129887
6719.4131901
6820.0133916
6920.6135930
7021.1137945
7121.7139960
7222.2141975
7322.8144991
7423.31461006
7523.91481021
7624.41501037
7725.01531053
7825.61551069
7926.11571085
8026.71601102
8127.21621118
8227.81651135
8328.31671152
8428.91701169
8529.41721186
8630.01751204
8730.61771221
8831.11801239
8931.71821257
9032.21851275
9132.81881293
9233.31901312
9333.91931330
9434.41961349
9535.01981368
9635.62011387
9736.12041407
9836.72071426
9937.22101446
10037.82131466
10138.32151486
10238.92181506
10339.42211526
10440.02241547
10540.62271568
10641.12301589
10741.72341610
10842.22371632
10942.82401653
11043.32431675
11143.92461697
11244.42491719
11345.02531742
11445.62561764
11546.12591787
11646.72631810
11747.22661833
11847.82691857
11948.32731880
12048.92761904
12149.42801928
12250.02831952
12350.62871977
12451.12902002
12551.72942027
12652.22982052
12752.83012077
12853.33052103
12953.93092128
13054.43122154

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-1270 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 4.512.5-15860.86
-55-48.3V 1.014.2-3980.98
-50-45.61.416.1101111.11
-45-42.83.518.2241261.26
-40-40.05.820.5401411.41
-35-37.28.323.0581591.59
-30-34.411.125.8761781.78
-25-31.714.128.8971981.98
-20-28.917.332.01192212.21
-15-26.120.935.51442452.45
-10-23.324.739.41702712.71
-5-20.628.843.51983003.00
0-17.833.247.92293303.30
5-15.038.052.72623633.63
10-12.243.157.82973983.98
15-9.448.563.23354364.36
20-6.754.469.13754764.76
25-3.960.675.34185195.19
30-1.167.281.94645655.65
351.774.389.05126146.14
404.481.896.55646656.65
457.289.8104.56197207.20
5010.098.2112.96777797.79
5512.8107121.97398408.40
6015.6117131.38049059.05
6518.3127141.38739749.74
7021.1137151.8945104610.46
7523.9148162.81021112311.23
8026.7160174.51102120312.03
8529.4172186.71186128812.88
9032.2185199.61275137613.76
9535.0198213.11368146914.69
10037.8213227.31466156715.67
10540.6227242.11568166916.69
11043.3243257.61675177617.76
11546.1259273.91787188818.88
12048.9276290.91904200620.06
12551.7294308.62027212821.28
13054.4312327.22154225622.56

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E)

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.