Refrigerant · HFC

R-152a pressure-temperature chart and data

Difluoroethane. Safety class A2, GWP 124. Blend component and aerosol propellant; rarely used alone in refrigeration. Flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-152a data sheet

NameDifluoroethane
TypeHFC
Safety classA2 — lower toxicity, flammable
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)124
Boils at 1 atm-11.2 °F (-24.0 °C)
Critical temperature235.9 °F (113.3 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating6.9 psig (48 kPa)
High side at 86 °F condensing85.4 psig (589 kPa)
Old cylinder colournone assigned
OilPOE / Mineral
Used forBlend component and aerosol propellant; rarely used alone in refrigeration. Flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-152a pressure / temperature chart

°F°CpsigkPa
-60-51.1V 22.3-76
-59-50.6V 22.1-75
-58-50.0V 21.8-74
-57-49.4V 21.6-73
-56-48.9V 21.3-72
-55-48.3V 21.0-71
-54-47.8V 20.7-70
-53-47.2V 20.4-69
-52-46.7V 20.2-68
-51-46.1V 19.9-67
-50-45.6V 19.5-66
-49-45.0V 19.2-65
-48-44.4V 18.9-64
-47-43.9V 18.6-63
-46-43.3V 18.2-62
-45-42.8V 17.9-60
-44-42.2V 17.5-59
-43-41.7V 17.1-58
-42-41.1V 16.8-57
-41-40.6V 16.4-55
-40-40.0V 16.0-54
-39-39.4V 15.6-53
-38-38.9V 15.2-51
-37-38.3V 14.7-50
-36-37.8V 14.3-48
-35-37.2V 13.9-47
-34-36.7V 13.4-45
-33-36.1V 12.9-44
-32-35.6V 12.5-42
-31-35.0V 12.0-41
-30-34.4V 11.5-39
-29-33.9V 11.0-37
-28-33.3V 10.5-35
-27-32.8V 9.9-34
-26-32.2V 9.4-32
-25-31.7V 8.9-30
-24-31.1V 8.3-28
-23-30.6V 7.7-26
-22-30.0V 7.1-24
-21-29.4V 6.5-22
-20-28.9V 5.9-20
-19-28.3V 5.3-18
-18-27.8V 4.7-16
-17-27.2V 4.0-14
-16-26.7V 3.3-11
-15-26.1V 2.7-9
-14-25.6V 2.0-7
-13-25.0V 1.3-4
-12-24.4V 0.5-2
-11-23.90.11
-10-23.30.53
-9-22.80.86
-8-22.21.28
-7-21.71.611
-6-21.12.014
-5-20.62.417
-4-20.02.819
-3-19.43.222
-2-18.93.625
-1-18.34.128
0-17.84.531
1-17.25.034
2-16.75.438
3-16.15.941
4-15.66.444
5-15.06.947
6-14.47.451
7-13.97.954
8-13.38.458
9-12.88.961
10-12.29.465
11-11.710.069
12-11.110.572
13-10.611.176
14-10.011.680
15-9.412.284
16-8.912.888
17-8.313.492
18-7.814.097
19-7.214.6101
20-6.715.2105
21-6.115.9109
22-5.616.5114
23-5.017.2118
24-4.417.9123
25-3.918.5128
26-3.319.2133
27-2.819.9137
28-2.220.6142
29-1.721.4147
30-1.122.1152
31-0.622.8157
320.023.6163
330.624.4168
341.125.1173
351.725.9179
362.226.7184
372.827.6190
383.328.4196
393.929.2202
404.430.1207
415.031.0213
425.631.8220
436.132.7226
446.733.6232
457.234.6238
467.835.5245
478.336.4251
488.937.4258
499.438.4265
5010.039.4271
5110.640.4278
5211.141.4285
5311.742.4292
5412.243.5300
5512.844.5307
5613.345.6314
5713.946.7322
5814.447.8330
5915.048.9337
6015.650.0345
6116.151.2353
6216.752.4361
6317.253.5369
6417.854.8377
6518.356.0386
6618.957.2394
6719.458.4403
6820.059.7412
6920.661.0420
7021.162.3429
7121.763.6438
7222.264.9448
7322.866.3457
7423.367.6466
7523.969.0476
7624.470.4485
7725.071.8495
7825.673.2505
7926.174.7515
8026.776.2525
8127.277.6535
8227.879.2546
8328.380.7556
8428.982.2567
8529.483.8578
8630.085.3588
8730.687.0599
8831.188.6611
8931.790.2622
9032.291.9633
9132.893.5645
9233.395.2657
9333.997.0668
9434.498.7680
9535.0100693
9635.6102705
9736.1104717
9836.7106730
9937.2108742
10037.8110755
10138.3111768
10238.9113781
10339.4115795
10440.0117808
10540.6119822
10641.1121835
10741.7123849
10842.2125863
10942.8127877
11043.3129892
11143.9131906
11244.4134921
11345.0136936
11445.6138951
11546.1140966
11646.7142981
11747.2145996
11847.81471012
11948.31491028
12048.91511044
12149.41541060
12250.01561076
12350.61581092
12451.11611109
12551.71631126
12652.21661143
12752.81681160
12853.31711177
12953.91731195
13054.41761213

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-152a pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 22.33.7-76260.26
-55-48.3V 21.04.4-71300.30
-50-45.6V 19.55.1-66350.35
-45-42.8V 17.95.9-60410.41
-40-40.0V 16.06.8-54470.47
-35-37.2V 13.97.9-47540.54
-30-34.4V 11.59.0-39620.62
-25-31.7V 8.910.3-30710.71
-20-28.9V 5.911.8-20810.81
-15-26.1V 2.713.4-9920.92
-10-23.30.515.131041.04
-5-20.62.417.1171181.18
0-17.84.519.2311331.33
5-15.06.921.6471491.49
10-12.29.424.1651661.66
15-9.412.226.9841861.86
20-6.715.229.91052062.06
25-3.918.533.21282292.29
30-1.122.136.81522542.54
351.725.940.61792802.80
404.430.144.82073093.09
457.234.649.32383403.40
5010.039.454.12713733.73
5512.844.559.23074084.08
6015.650.064.73454464.46
6518.356.070.73864874.87
7021.162.377.04295315.31
7523.969.083.74765775.77
8026.776.290.95256266.26
8529.483.898.55786796.79
9032.291.9106.66337357.35
9535.0100115.16937947.94
10037.8110124.27558578.57
10540.6119133.88229239.23
11043.3129144.08929939.93
11546.1140154.7966106710.67
12048.9151166.11044114511.45
12551.7163178.01126122712.27
13054.4176190.61213131413.14

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.