Refrigerant · HFO

R-1233zd(E) pressure-temperature chart and data

Chlorotrifluoropropene. Safety class A1, GWP 1. Low-pressure chillers replacing R-123 and R-245fa. Very low GWP.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-1233zd(E) data sheet

NameChlorotrifluoropropene
TypeHFO
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)1
Boils at 1 atm64.6 °F (18.1 °C)
Critical temperature330.3 °F (165.7 °C)
Temperature glidenone / very small
Low side at 5 °F evaporatingV 22.8 psig (-77 kPa)
High side at 86 °F condensing7.8 psig (54 kPa)
Old cylinder colournone assigned
OilPOE / Mineral
Used forLow-pressure chillers replacing R-123 and R-245fa. Very low GWP.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-1233zd(E) pressure / temperature chart

°F°CpsigkPa
-54-47.8V 28.9-98
-53-47.2V 28.9-98
-52-46.7V 28.8-98
-51-46.1V 28.8-97
-50-45.6V 28.7-97
-49-45.0V 28.7-97
-48-44.4V 28.6-97
-47-43.9V 28.6-97
-46-43.3V 28.5-97
-45-42.8V 28.5-96
-44-42.2V 28.4-96
-43-41.7V 28.4-96
-42-41.1V 28.3-96
-41-40.6V 28.3-96
-40-40.0V 28.2-95
-39-39.4V 28.1-95
-38-38.9V 28.1-95
-37-38.3V 28.0-95
-36-37.8V 27.9-95
-35-37.2V 27.9-94
-34-36.7V 27.8-94
-33-36.1V 27.7-94
-32-35.6V 27.6-94
-31-35.0V 27.6-93
-30-34.4V 27.5-93
-29-33.9V 27.4-93
-28-33.3V 27.3-93
-27-32.8V 27.2-92
-26-32.2V 27.1-92
-25-31.7V 27.1-92
-24-31.1V 27.0-91
-23-30.6V 26.9-91
-22-30.0V 26.8-91
-21-29.4V 26.7-90
-20-28.9V 26.5-90
-19-28.3V 26.4-90
-18-27.8V 26.3-89
-17-27.2V 26.2-89
-16-26.7V 26.1-88
-15-26.1V 26.0-88
-14-25.6V 25.9-88
-13-25.0V 25.7-87
-12-24.4V 25.6-87
-11-23.9V 25.5-86
-10-23.3V 25.3-86
-9-22.8V 25.2-85
-8-22.2V 25.0-85
-7-21.7V 24.9-84
-6-21.1V 24.7-84
-5-20.6V 24.6-83
-4-20.0V 24.4-83
-3-19.4V 24.3-82
-2-18.9V 24.1-82
-1-18.3V 23.9-81
0-17.8V 23.8-80
1-17.2V 23.6-80
2-16.7V 23.4-79
3-16.1V 23.2-79
4-15.6V 23.0-78
5-15.0V 22.8-77
6-14.4V 22.6-77
7-13.9V 22.4-76
8-13.3V 22.2-75
9-12.8V 22.0-75
10-12.2V 21.8-74
11-11.7V 21.6-73
12-11.1V 21.3-72
13-10.6V 21.1-71
14-10.0V 20.9-71
15-9.4V 20.6-70
16-8.9V 20.4-69
17-8.3V 20.1-68
18-7.8V 19.9-67
19-7.2V 19.6-66
20-6.7V 19.3-65
21-6.1V 19.0-64
22-5.6V 18.8-64
23-5.0V 18.5-63
24-4.4V 18.2-62
25-3.9V 17.9-61
26-3.3V 17.6-60
27-2.8V 17.3-58
28-2.2V 16.9-57
29-1.7V 16.6-56
30-1.1V 16.3-55
31-0.6V 15.9-54
320.0V 15.6-53
330.6V 15.2-52
341.1V 14.9-50
351.7V 14.5-49
362.2V 14.2-48
372.8V 13.8-47
383.3V 13.4-45
393.9V 13.0-44
404.4V 12.6-43
415.0V 12.2-41
425.6V 11.7-40
436.1V 11.3-38
446.7V 10.9-37
457.2V 10.4-35
467.8V 10.0-34
478.3V 9.5-32
488.9V 9.1-31
499.4V 8.6-29
5010.0V 8.1-28
5110.6V 7.6-26
5211.1V 7.1-24
5311.7V 6.6-22
5412.2V 6.1-21
5512.8V 5.6-19
5613.3V 5.0-17
5713.9V 4.5-15
5814.4V 3.9-13
5915.0V 3.4-11
6015.6V 2.8-9
6116.1V 2.2-7
6216.7V 1.6-5
6317.2V 1.0-3
6417.8V 0.4-1
6518.30.11
6618.90.43
6719.40.75
6820.01.17
6920.61.410
7021.11.712
7121.72.114
7222.22.417
7322.82.819
7423.33.121
7523.93.524
7624.43.826
7725.04.229
7825.64.632
7926.15.034
8026.75.437
8127.25.840
8227.86.242
8328.36.645
8428.97.048
8529.47.451
8630.07.854
8730.68.357
8831.18.760
8931.79.163
9032.29.666
9132.810.169
9233.310.573
9333.911.076
9434.411.579
9535.011.982
9635.612.486
9736.112.989
9836.713.493
9937.214.096
10037.814.5100
10138.315.0104
10238.915.6107
10339.416.1111
10440.016.6115
10540.617.2119
10641.117.8123
10741.718.4127
10842.218.9131
10942.819.5135
11043.320.1139
11143.920.7143
11244.421.3147
11345.022.0151
11445.622.6156
11546.123.2160
11646.723.9165
11747.224.5169
11847.825.2174
11948.325.9178
12048.926.5183
12149.427.2188
12250.027.9193
12350.628.6197
12451.129.4202
12551.730.1207
12652.230.8212
12752.831.6218
12853.332.3223
12953.933.1228
13054.433.8233

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-1233zd(E) pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-50-45.6V 28.70.6-9740.04
-45-42.8V 28.50.7-9650.05
-40-40.0V 28.20.8-9560.06
-35-37.2V 27.91.0-9470.07
-30-34.4V 27.51.2-9380.08
-25-31.7V 27.11.4-92100.10
-20-28.9V 26.51.7-90110.11
-15-26.1V 26.01.9-88130.13
-10-23.3V 25.32.3-86160.16
-5-20.6V 24.62.6-83180.18
0-17.8V 23.83.0-80210.21
5-15.0V 22.83.5-77240.24
10-12.2V 21.84.0-74280.28
15-9.4V 20.64.6-70310.31
20-6.7V 19.35.2-65360.36
25-3.9V 17.95.9-61410.41
30-1.1V 16.36.7-55460.46
351.7V 14.57.6-49520.52
404.4V 12.68.5-43590.59
457.2V 10.49.6-35660.66
5010.0V 8.110.7-28740.74
5512.8V 5.612.0-19820.82
6015.6V 2.813.3-9920.92
6518.30.114.811021.02
7021.11.716.4121131.13
7523.93.518.2241251.25
8026.75.420.1371381.38
8529.47.422.1511521.52
9032.29.624.3661671.67
9535.011.926.6821841.84
10037.814.529.21002012.01
10540.617.231.91192202.20
11043.320.134.81392402.40
11546.123.237.91602612.61
12048.926.541.21832842.84
12551.730.144.82073093.09
13054.433.848.52333353.35

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.