Refrigerant · HCFC

R-22 pressure-temperature chart and data

Chlorodifluoromethane. Safety class A1, GWP 1,810. Old residential and commercial A/C, heat pumps and refrigeration. Virgin supply is phased out; only reclaimed stock. Replaced by R-410A, R-407C, R-404A, R-407A.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-22 data sheet

NameChlorodifluoromethane
TypeHCFC
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0.055
Global warming (GWP, 100 yr)1,810
Boils at 1 atm-41.5 °F (-40.8 °C)
Critical temperature205.1 °F (96.2 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating28.3 psig (195 kPa)
High side at 86 °F condensing158 psig (1091 kPa)
Old cylinder colourLight green
OilMineral / AB (POE in retrofits)
Used forOld residential and commercial A/C, heat pumps and refrigeration. Virgin supply is phased out; only reclaimed stock. Replaced by R-410A, R-407C, R-404A, R-407A.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-22 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 11.9-40
-59-50.6V 11.4-39
-58-50.0V 10.9-37
-57-49.4V 10.3-35
-56-48.9V 9.8-33
-55-48.3V 9.2-31
-54-47.8V 8.6-29
-53-47.2V 8.0-27
-52-46.7V 7.4-25
-51-46.1V 6.7-23
-50-45.6V 6.1-21
-49-45.0V 5.4-18
-48-44.4V 4.8-16
-47-43.9V 4.1-14
-46-43.3V 3.4-11
-45-42.8V 2.7-9
-44-42.2V 1.9-7
-43-41.7V 1.2-4
-42-41.1V 0.4-1
-41-40.60.21
-40-40.00.64
-39-39.41.07
-38-38.91.49
-37-38.31.812
-36-37.82.215
-35-37.22.618
-34-36.73.121
-33-36.13.524
-32-35.64.028
-31-35.04.531
-30-34.44.934
-29-33.95.437
-28-33.35.941
-27-32.86.444
-26-32.26.948
-25-31.77.551
-24-31.18.055
-23-30.68.559
-22-30.09.163
-21-29.49.666
-20-28.910.270
-19-28.310.874
-18-27.811.479
-17-27.212.083
-16-26.712.687
-15-26.113.291
-14-25.613.996
-13-25.014.5100
-12-24.415.2105
-11-23.915.8109
-10-23.316.5114
-9-22.817.2119
-8-22.217.9124
-7-21.718.6129
-6-21.119.4134
-5-20.620.1139
-4-20.020.9144
-3-19.421.6149
-2-18.922.4155
-1-18.323.2160
0-17.824.0166
1-17.224.9171
2-16.725.7177
3-16.126.5183
4-15.627.4189
5-15.028.3195
6-14.429.1201
7-13.930.1207
8-13.331.0214
9-12.831.9220
10-12.232.8226
11-11.733.8233
12-11.134.8240
13-10.635.8247
14-10.036.8253
15-9.437.8260
16-8.938.8268
17-8.339.9275
18-7.840.9282
19-7.242.0290
20-6.743.1297
21-6.144.2305
22-5.645.3313
23-5.046.5320
24-4.447.6328
25-3.948.8337
26-3.350.0345
27-2.851.2353
28-2.252.5362
29-1.753.7370
30-1.155.0379
31-0.656.2388
320.057.5397
330.658.9406
341.160.2415
351.761.5424
362.262.9434
372.864.3443
383.365.7453
393.967.1463
404.468.6473
415.070.0483
425.671.5493
436.173.0503
446.774.5514
457.276.1524
467.877.6535
478.379.2546
488.980.8557
499.482.4568
5010.084.1580
5110.685.7591
5211.187.4603
5311.789.1614
5412.290.8626
5512.892.6638
5613.394.3651
5713.996.1663
5814.498.0675
5915.099.8688
6015.6102701
6116.1104714
6216.7105727
6317.2107740
6417.8109753
6518.3111767
6618.9113781
6719.4115795
6820.0117809
6920.6119823
7021.1121837
7121.7124852
7222.2126867
7322.8128881
7423.3130896
7523.9132912
7624.4134927
7725.0137943
7825.6139958
7926.1141974
8026.7144990
8127.21461007
8227.81481023
8328.31511040
8428.91531056
8529.41561073
8630.01581091
8730.61611108
8831.11631125
8931.71661143
9032.21681161
9132.81711179
9233.31741197
9333.91761216
9434.41791235
9535.01821253
9635.61851272
9736.11871292
9836.71901311
9937.21931331
10037.81961351
10138.31991371
10238.92021391
10339.42051412
10440.02081432
10540.62111453
10641.12141474
10741.72171496
10842.22201517
10942.82231539
11043.32261561
11143.92301583
11244.42331605
11345.02361628
11445.62391651
11546.12431674
11646.72461697
11747.22501721
11847.82531744
11948.32561768
12048.92601792
12149.42631817
12250.02671841
12350.62711866
12451.12741891
12551.72781917
12652.22821942
12752.82851968
12853.32891994
12953.92932020
13054.42972047

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-22 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 11.98.8-40610.61
-55-48.3V 9.210.2-31700.70
-50-45.6V 6.111.7-21810.81
-45-42.8V 2.713.4-9920.92
-40-40.00.615.341051.05
-35-37.22.617.3181201.20
-30-34.44.919.6341351.35
-25-31.77.522.1511531.53
-20-28.910.224.9701721.72
-15-26.113.227.9911931.93
-10-23.316.531.21142152.15
-5-20.620.134.81392402.40
0-17.824.038.71662672.67
5-15.028.343.01952962.96
10-12.232.847.52263283.28
15-9.437.852.52603623.62
20-6.743.157.82973983.98
25-3.948.863.53374384.38
30-1.155.069.73794804.80
351.761.576.24245265.26
404.468.683.34735745.74
457.276.190.85246266.26
5010.084.198.85806816.81
5512.892.6107.36387407.40
6015.6102116.37018028.02
6518.3111125.97678688.68
7021.1121136.18379399.39
7523.9132146.9912101310.13
8026.7144158.3990109210.92
8529.4156170.41073117511.75
9032.2168183.11161126212.62
9535.0182196.51253135513.55
10037.8196210.61351145214.52
10540.6211225.51453155415.54
11043.3226241.11561166216.62
11546.1243257.51674177517.75
12048.9260274.71792189418.94
12551.7278292.71917201820.18
13054.4297311.62047214821.48

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.