Pressure & vacuum tables

Vacuum, psi and kPa tables, water boiling point, altitude, refrigerant pressures in every unit.

Vacuum conversion

Vacuum (in. Hg)Absolute (mm Hg)Absolute (psia)Water column (ft)
29.92 (atmosphere)76014.733.4
287111432.2
266601329.9
246101227.6
225591125.3
205081023.0
18457920.7
16408818.4
14356716.1
12305613.8
10254511.5
820349.2
615236.9
410224.6
25112.3
0000

Atmosphere = 29.92 in. Hg = 14.7 psia = 760 mm Hg = 760,000 microns. 1 in. Hg = 25.4 mm Hg = 25,400 microns.

psia, psig and kPa

psiapsigkPa (absolute)
10590725
9075621
7560518
6045414
4530311
3015207
150100
10−569
5−1035
0−150

psia = psig + 14.7 at sea level (15 is a common shortcut). Use absolute pressure for gas-law math.

Water boiling point under vacuum

Water temp (°F)Vacuum (in. Hg)Microns
3529.725,170
4529.627,630
5529.4811,075
6529.3015,815
7529.0522,245
8528.7030,850
9528.2542,220
10527.6857,050
11526.9276,180
12525.96100,590

This is why a deep vacuum dries a system. Water at room temperature boils off at a few thousand microns.

Atmospheric pressure by elevation

Elevation (ft)Atmosphere (psia)
Sea level14.7
2,00013.7
4,00012.9
5,00012.2

Re-zero an analog gauge open to the air at the job elevation. Never adjust an absolute gauge.

Refrigerant pressure in every unit

Pick a refrigerant to see its pressure in every unit.

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.