Trane furnace error codes

75 codes (42 faults, 33 normal display and menu codes), plus 7 settings tables.

CodeMeaningSeverity / type
2 FlashesSystem lockoutHigh
3 FlashesDraft pressure errorHigh
4 FlashesOpen high limit deviceHigh
5 FlashesFlame sensed with no flame expectedHigh
6 Flashes115 V AC power reversed or poor groundingMedium
7 FlashesGas valve circuit errorHigh
8 FlashesLow flame sense signalHigh
9 FlashesIgnitor circuit or neutral-to-common voltageHigh
CL1Cooling, stage 1Normal status
CL2Cooling, stage 2Normal status
CP1Cooling / heat pump, stage 1 (single-stage models)Normal status
CP2Cooling / heat pump, stage 2Normal status
E01Furnace control internal failureHigh
E2.1Ignition retries exceeded - flame never proven (1 hour lockout)High
E2.2Flame recycles exceeded - flame lost after lighting (1 hour lockout)High
E2.31st stage gas valve not powered when it should be (10 times)High
E3.11st stage pressure switch (PS1) closed when it should be openMedium
E3.21st stage pressure switch (PS1) open when it should be closedMedium
E3.32nd stage pressure switch (PS2) closed when it should be openMedium
E3.42nd stage pressure switch (PS2) open when it should be closedMedium
E04Open limit (main limit, rollout or reverse airflow)High
E4.0Main high limit openHigh
E4.1Reverse airflow limit openHigh
E4.2Flame rollout switch openCritical
E05Flame sensed when no flame should be presentCritical
E6.1120 V polarity reversedMedium
E6.2Ground not detectedMedium
E6.3Igniter open or igniter relay faultHigh
E7.11st stage gas valve (MVL) powered with no callCritical
E7.2Redundant relay (HLO output) on with no callCritical
E08Low flame signal (still running)Low
E11Gas valve relay / valve circuit faultHigh
E12Control fuse openMedium
E13Blower motor size / OEM ID mismatchMedium
E14Configuration file errorMedium
E17Blower motor communication errorHigh
E23Menu data not received by combustion micro (CCM)Medium
E24Internal communication error between ACM and CCMMedium
E25Orientation sensor out of rangeLow
E26Return static pressure sensor out of range or not connectedLow
E27Return air thermistor out of range or not connectedLow
E28Supply air thermistor out of range or not connectedLow
HP1Heat pump, stage 1 demandNormal status
HP2Heat pump, stage 2 demandNormal status
Ht1Gas heat, stage 1 demandNormal status
Ht2Gas heat, stage 2 demandNormal status
L6FLast 6 faults menuMenu / mode display
tP1 to tP9Blower tap in useNormal status
---Faults cleared confirmationNormal status
ARFCalculated airflow readout (cfm x 10)Normal status
Both LEDs flashing togetherBluetooth pairing in progressNormal status
CoFContinuous fan demandNormal status
Continuous OFFCheck powerMedium
Continuous ONReplace integrated furnace controlHigh
CrControl code release numberMenu / mode display
FDFactory default reset doneMenu / mode display
Flashing FastNormal - call for heatNormal status
Flashing SlowNormal - no call for heatNormal status
HLdHold during run testNormal status
HtGas heating (single-stage models)Normal status
IdLIdle - no demandNormal status
LED continuous OFFNo power to controlHigh
LED continuous ONIFC board fault - replace controlHigh
LED flashing fastNormal - call for heatNormal status
LEDs both solidPower-upNormal status
MNRModel number recoveryMenu / mode display
SAtSupply air temperature readoutMenu / mode display
Status LED 1 flashActive demand (LED)Normal status
Status LED off, comm LED on/countingIdle (LEDs)Normal status
dFtOutdoor defrost demandNormal status
errActive alarm menuMenu / mode display
rAtReturn air temperature readoutMenu / mode display
rSPReturn static pressure readoutMenu / mode display
runRun test modeMenu / mode display
uErVerification test modeMenu / mode display

Settings and specs

Clearance to combustibles

Clearances · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.
  • 24 in. front service access.
  • 3 in. in front of the combustion air openings.
  • Downflow on combustible floor without coil needs BAYBASE205.
  • Garage: burners and igniter at least 18 in. above floor.

Source: Trane FNR-SVX003A-EN (S8V2) - Table 5

Return filter size by cabinet width

Filters · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.
  • Filters are field supplied and mounted outside the cabinet.
  • Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Source: Trane FNR-SVX003A-EN (S8V2) - Table 30

Return filter size by cabinet width

Filters · Trane S8B1, Trane S8X1, Trane S8X2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.
  • Filters are field supplied and mounted outside the cabinet.
  • Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Source: Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2) - Return Air Filters

Return filter size - upflow and downflow

Filters · Trane S9X1, Trane S9X2, Trane S9B1

Cabinet widthUpflowDownflow
17-1/2 in.1 - 16 x 25 x 1 in.2 - 14 x 20 x 1 in.
21 in.1 - 20 x 25 x 1 in.2 - 16 x 20 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.2 - 16 x 20 x 1 in.
  • Field supplied, installed outside the cabinet.
  • Upflow over 1600 CFM needs two returns or a bottom return.

Source: Trane 18-CE12D1-1D-EN (S9X1/S9X2/S9B1) - Return Air Filters

Clearance to combustibles

Clearances · Trane S9X1, Trane S9X2, Trane S9B1

PositionSidesBackTopFront / bottom / flue
Upright closet0 in.1 in.1 in.0 in.
Horizontal closet / alcove0 in.1 in.1 in.0 in.
Horizontal, flue out left0 in.1 in.1 in.0 in.
  • 24 in. front clearance recommended for service.
  • Furnace must sit level (slight tilt left/forward allowed) so condensate drains.

Source: Trane 18-CE12D1-1D-EN (S9X1/S9X2/S9B1) - Locations and Clearances

Return filter size - upflow and downflow

Filters · Trane S9V2

Cabinet widthUpflowDownflow
17-1/2 in.1 - 16 x 25 x 1 in.2 - 14 x 20 x 1 in.
21 in.1 - 20 x 25 x 1 in.2 - 16 x 20 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.2 - 16 x 20 x 1 in.
  • Field supplied, installed outside the cabinet.
  • Upflow over 1600 CFM needs two returns or a bottom return.

Source: Trane 18-CE19D1-1B-EN (S9V2) - Return Air Filters

Clearance to combustibles

Clearances · Trane S9V2

PositionSidesBackTopFront / bottom / flue
Upright closet0 in.1 in.1 in.0 in.
Horizontal closet / alcove0 in.1 in.1 in.0 in.
Horizontal, flue out left0 in.1 in.1 in.0 in.
  • 24 in. front clearance recommended for service.
  • Furnace must sit level (slight tilt left/forward allowed) so condensate drains.

Source: Trane 18-CE19D1-1B-EN (S9V2) - Locations and Clearances

Models covered

DH1B040A9241DH1B040A9241ADH1B065A9421DH1B065A9421ADH1C085A9481DH1C085A9481ADH1D110A9601DH1D110A9601AS8B1A026M2PSABS8B1A040M3PSABS8B1B040M2PSABS8B1B060M3PSABS8B1B060M4PSABS8B1B080M4PSABS8B1C080M5PSABS8B1C100M5PSABS8B1D120M5PSABS8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PDS8X1A026M2PSABS8X1A040M3PSABS8X1B040M2PSABS8X1B060M3PSABS8X1B060M4PSABS8X1B080M4PSABS8X1C080M5PSABS8X1C100M5PSABS8X1D120M5PSABS8X2A040M3PSABS8X2B060M3PSABS8X2B060M4PSABS8X2B080M4PSABS8X2C080M5PSABS8X2C100M5PSABS8X2D120M5PSABS9B1B040D3PSS9B1B040U3PSS9B1B060D3PSS9B1B060U4PSS9B1B080D4PSS9B1B080U4PSS9B1C080U5PSS9B1C100D5PSS9B1C100U5PSS9B1D120D5PSS9B1D120U5PSS9V2B040U3VSACS9V2B060U3VSACS9V2B080D4VSACS9V2B080U4VSACS9V2C100D4VSACS9V2C100U4VSACS9V2D120U5VSACS9X1B040D3PSS9X1B040U3PSS9X1B060D3PSS9X1B060U4PSS9X1B080D4PSS9X1B080U4PSS9X1C080U5PSS9X1C100D5PSS9X1C100U5PSS9X1D120D5PSS9X1D120U5PSS9X2B040D3PSS9X2B040U3PSS9X2B060D3PSS9X2B060U4PSS9X2B080D4PSS9X2B080U4PSS9X2C080U5PSS9X2C100D5PSS9X2C100U5PSS9X2D120D5PSS9X2D120U5PSUC1B060CUH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601UH1C080A9601AUH1C100A9481UH1C100A9481AUH1D100A9601UH1D100A9601AUH1D120A9601UH1D120A9601A

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.