Trane · Furnace
run Run test mode
What the display is showing
Lets a technician watch the inducer, igniter and blower step through their stages without firing the burner or running the outdoor unit. Option key holds a step (HLd). The test takes a short while to begin.
Applies to: S8V2, S8B1, S8X1, S8X2
What to do
- Press Menu until run appears, then press Option. The display flashes three times and the test starts.
- Steps inducer runs at 1st stage then 2nd stage (30 s each), igniter 10 s, then the blower at 1st-stage and 2nd-stage compressor speed and 1st-stage and 2nd-stage gas heat speed (10 s each). The sequence repeats two more times.
- Exit by pressing Menu briefly, cycling furnace power, or making a valid thermostat call.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
- Return filter size by cabinet width · Trane S8B1, Trane S8X1, Trane S8X2
Models that show this code
37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Other codes on the same units
- SAt Supply air temperature readout
- Status LED 1 flash Active demand (LED)
- Status LED off, comm LED on/counting Idle (LEDs)
- dFt Outdoor defrost demand
- err Active alarm menu
- rAt Return air temperature readout
- rSP Return static pressure readout
- uEr Verification test mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane S8V2 installation FNR-SVX003A-EN, Run Test Mode, p.57-58; Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, Display Codes, p.58. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.