Trane · Furnace

rAt Return air temperature readout

Menu / mode display Trane S8V2

What the display is showing

Menu item that shows the return air thermistor temperature.

Applies to: S8V2

What to do

  1. Press Menu until rAt appears, then press Option to read the value.

Settings for these units

Clearance to combustibles · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.

24 in. front service access.

3 in. in front of the combustion air openings.

Return filter size by cabinet width · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

Filters are field supplied and mounted outside the cabinet.

Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Models that show this code

12 models in Trane S8V2

S8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PD

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane S8V2 installation FNR-SVX003A-EN, Table 36 IFC display codes, p.59. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.