Trane · Furnace
E26 Return static pressure sensor out of range or not connected
What the control is telling you
The optional return static pressure kit (BAYFURNPTKT) reads out of range, or it is enabled but not plugged in. Furnace operation is not affected.
Applies to: Trane S8V2 only
Likely causes
- Kit enabled in app but not installed
- Harness unplugged
- Faulty transducer
Test and repair steps
- Check whether BAYFURNPTKT is actually installed; if not, disable it in the Link mobile app (disabled is factory default).
- If installed, confirm 5 VDC supply from the IFC and that the output voltage tracks the measured pressure.
- Replace the transducer if the output does not follow pressure.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
Models that show this code
12 models in Trane S8V2
Other codes on the same units
- E17 Blower motor communication error
- E23 Menu data not received by combustion micro (CCM)
- E24 Internal communication error between ACM and CCM
- E25 Orientation sensor out of range
- E27 Return air thermistor out of range or not connected
- E28 Supply air thermistor out of range or not connected
- HP1 Heat pump, stage 1 demand
- HP2 Heat pump, stage 2 demand
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.