Trane · Furnace
E23 Menu data not received by combustion micro (CCM)
What the control is telling you
The combustion control processor on the IFC has incomplete menu data.
Applies to: Trane S8V2 only
Likely causes
- Internal IFC data issue
Test and repair steps
- Turn power off for one minute and restore.
- If the error returns, replace the IFC.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
Models that show this code
12 models in Trane S8V2
Other codes on the same units
- E12 Control fuse open
- E13 Blower motor size / OEM ID mismatch
- E14 Configuration file error
- E17 Blower motor communication error
- E24 Internal communication error between ACM and CCM
- E25 Orientation sensor out of range
- E26 Return static pressure sensor out of range or not connected
- E27 Return air thermistor out of range or not connected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.