Trane · Furnace

Ht1 Gas heat, stage 1 demand

Normal status Trane S8V2Trane S8X2

What the display is showing

The display alternates every 2 seconds between Ht1 and the airflow readout while first-stage gas heat is called. The status follows the 24 VAC on the thermostat terminals.

Applies to: S8V2 and S8X2

Settings for these units

Clearance to combustibles · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.

24 in. front service access.

3 in. in front of the combustion air openings.

Return filter size by cabinet width · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

Filters are field supplied and mounted outside the cabinet.

Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Models that show this code

19 models in Trane S8V2, Trane S8X2

S8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PDS8X2A040M3PSABS8X2B060M3PSABS8X2B060M4PSABS8X2B080M4PSABS8X2C080M5PSABS8X2C100M5PSABS8X2D120M5PSAB

Other codes on the same units

  • E27 Return air thermistor out of range or not connected
  • E28 Supply air thermistor out of range or not connected
  • HP1 Heat pump, stage 1 demand
  • HP2 Heat pump, stage 2 demand
  • Ht2 Gas heat, stage 2 demand
  • L6F Last 6 faults menu
  • tP1 to tP9 Blower tap in use
  • --- Faults cleared confirmation

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane S8V2 installation FNR-SVX003A-EN, Figure 73, p.58; Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, System Status Menu p.57 and Sequence of Operation p.60. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.