Trane · Furnace

8 Flashes Low flame sense signal

High severity AUH1B

What the control is telling you

Flame sensor signal is weak.

Applies to: Integrated furnace control

Likely causes

  • Low flame sense signal

Settings for these units

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane installer's manual (AUH1B040A9241A), p. 39. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.