Trane · Furnace
E2.2 Flame recycles exceeded - flame lost after lighting (1 hour lockout)
What the control is telling you
Flame was proven and then dropped out 10 times in one heat call, so the control locked out for one hour.
Applies to: Trane S8V2 (80%, 2-stage, variable speed, Link) and S8B1 / S8X1 / S8X2 (80%, 1- and 2-stage)
Likely causes
- Dirty or badly placed flame sensor
- Poor ground or loose sensor wiring
- Dirty burners
- Manifold pressure not held (weak supply)
- Gas valve dropping out
Test and repair steps
- Reset by cycling power and run 1st stage heat with other gas appliances on.
- Read flame signal on the FP pads (DC volts, 1 VDC = 1 microamp); 0.75 to 3.0 is normal.
- If it is low, clean the flame sensor, check its location, its wire and the burner ground.
- Connect a manometer to the manifold tap and confirm about 1.7 in. W.C. NG / 6.0 in. W.C. LP is held through the run.
- If manifold pressure sags, check inlet supply pressure and correct the gas supply before touching the regulator.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
- Return filter size by cabinet width · Trane S8B1, Trane S8X1, Trane S8X2
Models that show this code
37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Other codes on the same units
- E01 Furnace control internal failure
- E2.1 Ignition retries exceeded - flame never proven (1 hour lockout)
- E2.3 1st stage gas valve not powered when it should be (10 times)
- E3.1 1st stage pressure switch (PS1) closed when it should be open
- E3.2 1st stage pressure switch (PS1) open when it should be closed
- E3.3 2nd stage pressure switch (PS2) closed when it should be open
- E3.4 2nd stage pressure switch (PS2) open when it should be closed
- E04 Open limit (main limit, rollout or reverse airflow)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts); Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2 installer's guide) - section Integrated Furnace Control Display Codes, Error Codes. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.