Trane · Furnace

E3.3 2nd stage pressure switch (PS2) closed when it should be open

Medium severity Trane S8V2Trane S8X2

What the control is telling you

PS2 reads closed before 2nd stage was called. Usually wiring or tube routing rather than the switch.

Applies to: Trane S8V2 and S8X2 (2-stage models with PS2)

Likely causes

  • Incorrect PS2 wiring or hose
  • PS2 mounted in the wrong orientation for the furnace position
  • Stuck switch

Test and repair steps

  1. Check PS2 wiring and hose routing.
  2. Make sure PS2 is rotated correctly for the installed orientation (see the combustion air conversion section).
  3. Cycle power off and on, then measure across PS2 (brown to yellow) with the inducer on low: 0 V means closed.
  4. If PS2 reads closed at low inducer speed, replace the switch.

Settings for these units

Clearance to combustibles · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.

24 in. front service access.

3 in. in front of the combustion air openings.

Return filter size by cabinet width · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

Filters are field supplied and mounted outside the cabinet.

Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Models that show this code

19 models in Trane S8V2, Trane S8X2

S8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PDS8X2A040M3PSABS8X2B060M3PSABS8X2B060M4PSABS8X2B080M4PSABS8X2C080M5PSABS8X2C100M5PSABS8X2D120M5PSAB

Other codes on the same units

  • E2.2 Flame recycles exceeded - flame lost after lighting (1 hour lockout)
  • E2.3 1st stage gas valve not powered when it should be (10 times)
  • E3.1 1st stage pressure switch (PS1) closed when it should be open
  • E3.2 1st stage pressure switch (PS1) open when it should be closed
  • E3.4 2nd stage pressure switch (PS2) open when it should be closed
  • E04 Open limit (main limit, rollout or reverse airflow)
  • E4.0 Main high limit open
  • E4.1 Reverse airflow limit open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts); Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2 installer's guide) - section Integrated Furnace Control Display Codes, Error Codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.