Trane · Furnace

E2.3 1st stage gas valve not powered when it should be (10 times)

High severity Trane S8V2Trane S8B1Trane S8X1Trane S8X2

What the control is telling you

The control did not see 24 VAC on the MVL (1st stage valve) output when it expected it, 10 times in one heat call, and locks out for an hour. The S8V2 flowchart index words this as valve energized when it should not be; the code table and diagram say not energized.

Applies to: Trane S8V2 (80%, 2-stage, variable speed, Link) and S8B1 / S8X1 / S8X2 (80%, 1- and 2-stage)

Likely causes

  • Interrupted 24 V circuit (blower door switch, unplugged harness)
  • Power interruption or wind gust during the cycle
  • IFC gas valve relay fault

Test and repair steps

  1. Cycle power and call for 1st stage heat.
  2. Check that the blower door is closed and all plugs are seated.
  3. Measure manifold pressure during the call; if the minimum is held, look for intermittent power or wiring breaks.
  4. If manifold pressure is not held, check and correct incoming supply pressure.
  5. If wiring and supply are good and the code returns, replace the IFC.

Settings for these units

Clearance to combustibles · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.

24 in. front service access.

3 in. in front of the combustion air openings.

Return filter size by cabinet width · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

Filters are field supplied and mounted outside the cabinet.

Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Models that show this code

37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2

S8B1A026M2PSABS8B1A040M3PSABS8B1B040M2PSABS8B1B060M3PSABS8B1B060M4PSABS8B1B080M4PSABS8B1C080M5PSABS8B1C100M5PSABS8B1D120M5PSABS8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PDS8X1A026M2PSABS8X1A040M3PSABS8X1B040M2PSABS8X1B060M3PSABS8X1B060M4PSABS8X1B080M4PSABS8X1C080M5PSABS8X1C100M5PSABS8X1D120M5PSABS8X2A040M3PSABS8X2B060M3PSABS8X2B060M4PSABS8X2B080M4PSABS8X2C080M5PSABS8X2C100M5PSABS8X2D120M5PSAB

Other codes on the same units

  • CP2 Cooling / heat pump, stage 2
  • E01 Furnace control internal failure
  • E2.1 Ignition retries exceeded - flame never proven (1 hour lockout)
  • E2.2 Flame recycles exceeded - flame lost after lighting (1 hour lockout)
  • E3.1 1st stage pressure switch (PS1) closed when it should be open
  • E3.2 1st stage pressure switch (PS1) open when it should be closed
  • E3.3 2nd stage pressure switch (PS2) closed when it should be open
  • E3.4 2nd stage pressure switch (PS2) open when it should be closed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts); Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2 installer's guide) - section Integrated Furnace Control Display Codes, Error Codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.