Trane · Furnace

Cr Control code release number

Menu / mode display Trane S8V2Trane S8B1Trane S8X1Trane S8X2

What the display is showing

Read-only menu item that shows the software release of the control.

Applies to: S8V2, S8B1, S8X1, S8X2

What to do

  1. Press Menu until Cr appears, then press Option.

Settings for these units

Clearance to combustibles · Trane S8V2

Cabinet widthVertical sides / topHorizontal sides / top
14.5 in.0 / 1 in.1 / 2 in.
17.5 in.0 / 1 in.1 / 2 in.
21.0 in.0 / 1 in.1 / 3 in.
24.5 in.0 / 1 in.1 / 5 in.

24 in. front service access.

3 in. in front of the combustion air openings.

Return filter size by cabinet width · Trane S8V2

Cabinet widthFilter
14-1/2 in.1 - 14 x 25 x 1 in.
17-1/2 in.1 - 16 x 25 x 1 in.
21 in.1 - 20 x 25 x 1 in.
24-1/2 in.1 - 24 x 25 x 1 in.

Filters are field supplied and mounted outside the cabinet.

Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.

Models that show this code

37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2

S8B1A026M2PSABS8B1A040M3PSABS8B1B040M2PSABS8B1B060M3PSABS8B1B060M4PSABS8B1B080M4PSABS8B1C080M5PSABS8B1C100M5PSABS8B1D120M5PSABS8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PDS8X1A026M2PSABS8X1A040M3PSABS8X1B040M2PSABS8X1B060M3PSABS8X1B060M4PSABS8X1B080M4PSABS8X1C080M5PSABS8X1C100M5PSABS8X1D120M5PSABS8X2A040M3PSABS8X2B060M3PSABS8X2B060M4PSABS8X2B080M4PSABS8X2C080M5PSABS8X2C100M5PSABS8X2D120M5PSAB

Other codes on the same units

  • --- Faults cleared confirmation
  • ARF Calculated airflow readout (cfm x 10)
  • Both LEDs flashing together Bluetooth pairing in progress
  • CoF Continuous fan demand
  • FD Factory default reset done
  • HLd Hold during run test
  • Ht Gas heating (single-stage models)
  • IdL Idle - no demand

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane S8V2 installation FNR-SVX003A-EN, Table 36, p.59; Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, Display Codes, p.58. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.