Rheem heat pump error codes

47 codes (36 faults, 11 normal display and menu codes), plus 1 settings tables.

CodeMeaningSeverity / type
0Standby - no call for operationNormal status
01Long run time (compressor)Medium
1 flash (L terminal)L-terminal fault output: Long run cycle or low pressureMedium
02High side fault (compressor limit opened 4 times)High
2 flashes (L terminal)L-terminal fault output: High pressure control tripHigh
03Short cyclingMedium
3 flashes (L terminal)L-terminal fault output: Unit short cyclingMedium
4 flashes (L terminal)L-terminal fault output: Locked rotorHigh
05Open circuit - compressor will not runHigh
5 flashes (L terminal)L-terminal fault output: Compressor will not run, open circuitHigh
06Compressor open start circuitHigh
6 flashes (L terminal)L-terminal fault output: Open start circuitHigh
07Compressor open run circuitHigh
7 flashes (L terminal)L-terminal fault output: Open run circuitHigh
8 flashes (L terminal)L-terminal fault output: Control mis-operationHigh
09Low secondary (control) voltageMedium
9 flashes (L terminal)L-terminal fault output: Low control voltageMedium
21Low pressure control (LPC) openMedium
27Low line voltage or no line voltageMedium
28High line voltageMedium
29High pressure control (HPC) openHigh
30ICC fuse openMedium
80Low airflowMedium
83Condenser coil temperature sensor faultMedium
84Outdoor ambient temperature sensor faultLow
90Communication faultMedium
93Internal control faultHigh
d1No shared dataMedium
d3Airflow CFM mismatchMedium
d4Memory card invalid for deviceMedium
d8Old shared dataLow
L4Locked rotor lockoutHigh
L6Open start circuit lockoutHigh
L7Open run circuit lockoutHigh
L21Low pressure control lockoutHigh
Y1 LED solid redRed Y1 LED - call for compressor operationNormal status
C (upper case)Second-stage coolingNormal status
Defrost test (SW2)Forced defrost testMenu / mode display
Fault recall mode (TEST + SW2)Review stored faults on the ICC displayMenu / mode display
Flashing c / C / h / HAnti-short-cycle (3 min) or minimum-run (30 s) timer activeLow
H (upper case)Second-stage heat pump heatingNormal status
PCompressor protector tripHigh
Test mode (TEST button)ICC test mode and short-cycle bypassMenu / mode display
cFirst-stage coolingNormal status
dDefrost activeNormal status
hFirst-stage heat pump heatingNormal status
tTest mode activeNormal status

Settings and specs

Outdoor unit clearances

Clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)
  • Do not reduce the 60 in. discharge or 24 in. service clearances.
  • Inlet clearances under 6 in. reduce capacity and efficiency.
  • Cabinet: 33 in. high, 44-3/4 in. long, 31-1/2 in. wide (all sizes).

Source: Rheem/Ruud (-)PRL-JEC Installation Instructions 92-20522-63-06, Figure 1 and 3.3-3.4, PDF p.9 (printed p.6); PDF p.11 (printed p.8)

Models covered

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.