Rheem · Heat pump
Fault recall mode (TEST + SW2) Review stored faults on the ICC display
What the display is showing
Shows the stored fault history on the dual display. Entering and leaving the mode lights the top and bottom segments. Faults scroll automatically, newest first, with the top-right segment lit between them. Up to six faults are kept (max three identical in a row). A 0 means nothing is stored. The mode exits by itself after the last fault.
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
What to do
- Press TEST and SW2 together with insulated probes for one second and release.
- Watch the display scroll through the stored faults, newest first.
- Wait for it to exit automatically.
- To erase the history hold TEST and SW2 together for five seconds and release; the top and bottom segments flash to confirm.
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- L21 Low pressure control lockout
- Y1 LED solid red Red Y1 LED - call for compressor operation
- C (upper case) Second-stage cooling
- Defrost test (SW2) Forced defrost test
- Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
- H (upper case) Second-stage heat pump heating
- P Compressor protector trip
- Test mode (TEST button) ICC test mode and short-cycle bypass
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.5, pp.23-24. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.