Rheem · Heat pump

Test mode (TEST button) ICC test mode and short-cycle bypass

Menu / mode display Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the display is showing

Pressing the TEST button resets any active-protection lockout and the 3-minute anti-short-cycle timer, and energizes the unit even without a call. Use an insulated probe. A momentary t is shown if a timer was running.

Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC

What to do

  1. Use an insulated probe to press TEST for one second, then let go.
  2. If a call is present, the compressor and outdoor fan start and the display settles on c, C, h or H.
  3. If no call is present, a steady t shows and the compressor runs about 5 seconds.

Settings for these units

Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)

Do not reduce the 60 in. discharge or 24 in. service clearances.

Inlet clearances under 6 in. reduce capacity and efficiency.

Models that show this code

4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.5, p.23. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.