Rheem · Heat pump
H (upper case) Second-stage heat pump heating
What the display is showing
Capital H steady on the display: second-stage (high) heat-pump heating is running. Normal.
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- C (upper case) Second-stage cooling
- Defrost test (SW2) Forced defrost test
- Fault recall mode (TEST + SW2) Review stored faults on the ICC display
- Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
- P Compressor protector trip
- Test mode (TEST button) ICC test mode and short-cycle bypass
- c First-stage cooling
- d Defrost active
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.3 and 12.6, pp.19-25. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.