Rheem · Heat pump

P Compressor protector trip

High severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

There is a call for the compressor but the ICC measures no compressor current, so the compressor's internal motor protector is assumed open. If the protector does not reset within 4 hours the display changes to code 05.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Compressor internal motor protector open (overheated compressor)
  • Line voltage to compressor disconnected

Test and repair steps

  1. Confirm line voltage is present at the unit and at the ICC L1/L2 lugs.
  2. Allow the compressor to cool; the internal overload can take up to 2 hours to reset before you condemn the compressor.
  3. Look for overheating causes low/high charge, dirty outdoor coil, outdoor fan not running, low or high line voltage.
  4. Check the run capacitor for damage, wrong value or miswiring.
  5. Check for broken wires, loose connectors or a miswired compressor.
  6. Check compressor windings for continuity.
  7. If P persists past 4 hours the ICC will show 05 - continue with the 05 checks.

Settings for these units

Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)

Do not reduce the 60 in. discharge or 24 in. service clearances.

Inlet clearances under 6 in. reduce capacity and efficiency.

Models that show this code

4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.4 Active Compressor Protection Mode / 12.6 ICC Diagnostic Codes, p.25, 29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.