Rheem · Heat pump
Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
What the control is telling you
A flashing mode letter means the ICC has a call (c = 1st-stage cool, C = 2nd-stage cool, h = 1st-stage heat pump, H = 2nd-stage heat pump) but is holding the compressor on its 3-minute anti-short-cycle timer or 30-second minimum-run timer. Not a fault. Note: some pages of this manual show h1/h2 instead of h/H.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Compressor recently stopped (3-minute delay between compressor runs)
- Call removed less than 30 seconds after start (minimum run timer)
Test and repair steps
- Wait for the timer to finish; the letter turns steady when the compressor runs.
- To skip the delay, press TEST for 1 second and release; display shows 't', then compressor and outdoor fan start.
- If the letter flashes repeatedly with constant short runs, check fault history for code 03 (short cycling).
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- Y1 LED solid red Red Y1 LED - call for compressor operation
- C (upper case) Second-stage cooling
- Defrost test (SW2) Forced defrost test
- Fault recall mode (TEST + SW2) Review stored faults on the ICC display
- H (upper case) Second-stage heat pump heating
- P Compressor protector trip
- Test mode (TEST button) ICC test mode and short-cycle bypass
- c First-stage cooling
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.3 ICC Control Operation / 12.6 ICC Diagnostic Codes, p.23-25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.