Rheem · Heat pump
Defrost test (SW2) Forced defrost test
What the display is showing
With the unit running in heat-pump mode, pressing the SW2 pushbutton forces a defrost that runs until the termination temperature is reached or 14 minutes pass. Pressing SW2 again ends the test. If the unit goes into and out of defrost, the control is working.
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
What to do
- Set the thermostat to heat and make a heat call.
- Press SW2 for one second with the unit running in heat-pump mode.
- Watch the unit enter defrost; press SW2 again to stop the test early.
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- L7 Open run circuit lockout
- L21 Low pressure control lockout
- Y1 LED solid red Red Y1 LED - call for compressor operation
- C (upper case) Second-stage cooling
- Fault recall mode (TEST + SW2) Review stored faults on the ICC display
- Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
- H (upper case) Second-stage heat pump heating
- P Compressor protector trip
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem PRL-JEC Installation Instructions, 8.4-8.5 Defrost Test Mode. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.