Rheem · Heat pump

Defrost test (SW2) Forced defrost test

Menu / mode display Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the display is showing

With the unit running in heat-pump mode, pressing the SW2 pushbutton forces a defrost that runs until the termination temperature is reached or 14 minutes pass. Pressing SW2 again ends the test. If the unit goes into and out of defrost, the control is working.

Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC

What to do

  1. Set the thermostat to heat and make a heat call.
  2. Press SW2 for one second with the unit running in heat-pump mode.
  3. Watch the unit enter defrost; press SW2 again to stop the test early.

Settings for these units

Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)

Do not reduce the 60 in. discharge or 24 in. service clearances.

Inlet clearances under 6 in. reduce capacity and efficiency.

Models that show this code

4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem PRL-JEC Installation Instructions, 8.4-8.5 Defrost Test Mode. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.