Rheem · Heat pump

L21 Low pressure control lockout

High severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

Active protection after repeated LPC trips. Cooling: LPC opened 3 times in one call - hard lockout. Heating: 3 trips within 120 minutes in one call - hard lockout; or 3 trips in one call with outdoor ambient below 5°F - soft lockout that clears by itself once ambient rises above 5°F. Display alternates L and 21.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Low refrigerant charge
  • Frozen indoor or outdoor coil
  • Dirty indoor coil/filter or indoor blower not running (cooling)
  • Outdoor fan not running (heating)
  • TXV not working correctly

Test and repair steps

  1. If heating and outdoor temperature is below 5°F, wait until it rises above 5°F before further diagnosis (soft lockout clears itself).
  2. Work through the code 21 checks airflow, coil icing, fans, charge, TXV.
  3. Read stored faults press TEST and SW2 together for 1 second (insulated probes); up to 6 faults scroll, newest first.
  4. Reset the ICC after the cause is fixed press TEST for 1 second with an insulated probe (preferred), or cycle 24VAC (pull R or C) or cycle line power.

Settings for these units

Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)

Do not reduce the 60 in. discharge or 24 in. service clearances.

Inlet clearances under 6 in. reduce capacity and efficiency.

Models that show this code

4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.4 Active Compressor Protection Mode / 12.6 ICC Diagnostic Codes, p.24, 30. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.