Rheem · Heat pump

L4 Locked rotor lockout

High severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

Compressor ran less than 15 seconds on four (4) consecutive starts during the same call; the ICC locks out the compressor (display flashes L then 04/4). Manual reset required. Reported as 4 flashes on the L terminal.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Bad run capacitor
  • Low line voltage
  • Excess refrigerant in compressor (flooding/migration)
  • Seized compressor bearings

Test and repair steps

  1. Test the run capacitor and replace if out of spec.
  2. Measure line voltage at the compressor while starting; it must be within ±10% of nameplate (197-253V for 208/230V units).
  3. Make sure the crankcase heater works; at startup or after a long shutdown it should be powered 12 hours before starting the compressor.
  4. Check charge for overcharge/flooding.
  5. Check compressor windings for correct ohms and ground.
  6. Hard-start components are factory installed - verify they are intact.
  7. Reset the ICC after the cause is fixed press TEST for 1 second with an insulated probe (preferred), or cycle 24VAC (pull R or C) or cycle line power.

Settings for these units

Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

LocationMinimum
Above unit (fan discharge)60 in. [1524 mm]
Coil air inlets (3 sides)6 in. [152 mm]
Service access side24 in. [610 mm]
Between two units (grille sides aligned)12 in. total (6 in. per unit)

Do not reduce the 60 in. discharge or 24 in. service clearances.

Inlet clearances under 6 in. reduce capacity and efficiency.

Models that show this code

4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Other codes on the same units

  • d1 No shared data
  • d3 Airflow CFM mismatch
  • d4 Memory card invalid for device
  • d8 Old shared data
  • L6 Open start circuit lockout
  • L7 Open run circuit lockout
  • L21 Low pressure control lockout
  • Y1 LED solid red Red Y1 LED - call for compressor operation

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.4 Active Compressor Protection Mode / 12.6 ICC Diagnostic Codes, p.25, 29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.