Rheem · Heat pump
d1 No shared data
What the control is telling you
The control has no shared (unit) data.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Memory card missing, damaged or wrong
Test and repair steps
- Check the memory card is installed and tethered to this unit.
- Replace the memory card with one holding the correct system information (order from Pro Stock).
- Never use a memory card from a different unit.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes / 18.2 Replacement of Control Board, p.29, 31, 43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.