Rheem · Heat pump
83 Condenser coil temperature sensor fault
What the control is telling you
The coil sensor reads an abnormally low or high coil temperature. Defrost depends on this sensor.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Failed coil sensor
- Sensor not installed correctly
Test and repair steps
- Check that the coil sensor is clipped to the top tube of the outdoor coil at the point fed from the expansion device (short 3/8 inch tube).
- Check the sensor connector on the ICC.
- Replace the sensor if readings are abnormal.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.