Rheem · Heat pump
80 Low airflow
What the control is telling you
The ICC detects that the indoor unit cannot provide the minimum airflow the outdoor unit needs.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Indoor air mover misapplied or wrong size for the outdoor unit
Test and repair steps
- Confirm the air handler/furnace model is a matched, properly sized communicating unit.
- Check for dirty filter, closed registers or restricted ducts.
- Replace the indoor unit with a properly sized one if misapplied.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.