29 High pressure control (HPC) open
What the control is telling you
The ICC sees the HPC open. HPC opens near 610 PSIG and closes near 420 PSIG (the General Troubleshooting Chart elsewhere says 450 PSIG - manual inconsistency). Reported as 2 flashes on the L terminal.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Dirty outdoor coil (cooling)
- Outdoor fan not running (cooling)
- Dirty indoor coil or filter (heating)
- Indoor blower not running (heating)
- Liquid line restriction
- Refrigerant overcharge
- Non-condensables in system
Test and repair steps
- Cooling clean the outdoor coil, verify outdoor fan motor/blade/rotation, check for discharge air recirculation.
- Heating replace filter, check the indoor coil and blower operation and speed.
- Check for a restricted liquid line or filter drier.
- Check charge; recover if overcharged. If non-condensables are suspected, recover, evacuate to 500 microns and recharge.
- Check HPC wiring at the ICC HPC input.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.