Rheem · Heat pump

21 Low pressure control (LPC) open

Medium severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

The ICC sees the LPC open. The LPC opens near 15 PSIG and closes near 40 PSIG; it is ignored for the first 90 seconds of compressor run and during defrost.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Low refrigerant charge
  • Frozen indoor coil (cooling)
  • Dirty indoor coil or filter (cooling)
  • Indoor blower not running (cooling)
  • Frozen outdoor coil (heating)
  • Outdoor fan not running (heating)
  • Expansion valve (TXV) not working correctly

Test and repair steps

  1. Cooling replace the filter, check the indoor coil for dirt/ice and verify the indoor blower runs.
  2. Heating check the outdoor coil for ice and that the outdoor fan runs; force a defrost test (SW2) to check defrost.
  3. Check suction pressure and charge; leak-test if low.
  4. Check TXV operation (superheat, bulb mounting, equalizer line).
  5. Check LPC wiring at the ICC LPC input.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.