Rheem · Heat pump

27 Low line voltage or no line voltage

Medium severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

The ICC detects low or missing line voltage.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Low utility voltage
  • Tripped breaker/fuse or open disconnect
  • Loose or undersized power wiring

Test and repair steps

  1. Measure line voltage at the disconnect and at the unit; operating range for 208/230V units is 197-253V.
  2. Check fuses/breaker and disconnect.
  3. Check and tighten wiring connections at the ICC L1/L2 lugs (torque per wire size, check annually).
  4. If the utility supply is low, have it corrected before further diagnosis.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.