Rheem · Heat pump
h First-stage heat pump heating
What the display is showing
Lowercase h steady on the display: first-stage heat-pump heating is running. Normal. (A flashing h means the anti-short-cycle timer or the 30-second minimum-run timer is still counting.)
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- Fault recall mode (TEST + SW2) Review stored faults on the ICC display
- Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
- H (upper case) Second-stage heat pump heating
- P Compressor protector trip
- Test mode (TEST button) ICC test mode and short-cycle bypass
- c First-stage cooling
- d Defrost active
- t Test mode active
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.3 and 12.6, pp.19-25. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.