Rheem · Heat pump
3 flashes (L terminal) L-terminal fault output: Unit short cycling
What the control is telling you
Equivalent to code 03. Shown on an L-terminal compatible conventional thermostat when the unit is wired 24VAC (non-communicating).
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Thermostat wiring or location
Test and repair steps
- Read the ICC display.
- Follow code 03 checks.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.7 Conventional 24VAC Thermostat Control Wiring (L terminal output), p.31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.