Rheem · Heat pump
02 High side fault (compressor limit opened 4 times)
What the control is telling you
Compressor limit has opened four (4) times within one call for operation. The manual's code table is layered with an older draft that calls 02 'High Pressure Control Open' and points to codes 21/L21/29/L29; treat 02 as a high-side (high head) problem either way.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Dirty outdoor coil (cooling)
- Outdoor fan not running (cooling)
- Dirty indoor coil or filter (heating)
- Indoor blower not running (heating)
- Liquid line restriction
- Refrigerant overcharge
Test and repair steps
- Cooling mode clean the outdoor coil and verify the outdoor fan motor runs and turns the right way.
- Heating mode replace the filter, check the indoor coil and confirm the indoor blower runs.
- Check for liquid line or filter-drier restriction (temperature drop across the drier).
- Check charge against the charging chart; recover refrigerant if overcharged.
- Check for recirculation of discharge air around the outdoor unit.
- Read stored faults press TEST and SW2 together for 1 second (insulated probes); up to 6 faults scroll, newest first.
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- 0 Standby - no call for operation
- 01 Long run time (compressor)
- 1 flash (L terminal) L-terminal fault output: Long run cycle or low pressure
- 2 flashes (L terminal) L-terminal fault output: High pressure control trip
- 03 Short cycling
- 3 flashes (L terminal) L-terminal fault output: Unit short cycling
- 4 flashes (L terminal) L-terminal fault output: Locked rotor
- 05 Open circuit - compressor will not run
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.