Rheem · Heat pump
01 Long run time (compressor)
What the control is telling you
The compressor has run continuously for more than 18 hours in cooling mode. On a conventional thermostat L terminal this is reported as 1 flash.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Low refrigerant charge
- Substantial duct leakage
- Dirty indoor air filter
- Dirty outdoor coil
Test and repair steps
- Replace or clean the indoor air filter.
- Clean the outdoor coil.
- Check refrigerant charge using the unit charging chart (liquid pressure method) after 15-30 minutes of stable run; check subcooling (normal 9-12°F).
- Leak-check the system if undercharged; repair before recharging.
- Inspect ducts for major leakage and confirm the unit is not undersized for the load.
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- 0 Standby - no call for operation
- 1 flash (L terminal) L-terminal fault output: Long run cycle or low pressure
- 02 High side fault (compressor limit opened 4 times)
- 2 flashes (L terminal) L-terminal fault output: High pressure control trip
- 03 Short cycling
- 3 flashes (L terminal) L-terminal fault output: Unit short cycling
- 4 flashes (L terminal) L-terminal fault output: Locked rotor
- 05 Open circuit - compressor will not run
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.