Rheem · Heat pump
05 Open circuit - compressor will not run
What the control is telling you
There is a call for the compressor but no current in either the start or run winding circuits, or a protector trip has lasted more than 4 hours. The ICC retries every 5 minutes for 4 tries, then every 20 minutes for up to 4 hours. Reported as 5 flashes on the L terminal.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Compressor internal protector open
- Damaged, wrong or miswired run capacitor
- Broken wire, loose connector or miswired compressor
- Open compressor winding
Test and repair steps
- Check for an open compressor internal protector (let the compressor cool; can take up to 2 hours).
- Check the run capacitor for damage, wrong value or miswiring.
- Check for broken wires, loose connectors or a miswired compressor.
- Check compressor windings for continuity.
- Verify line voltage reaches the compressor through the ICC compressor relay (K2).
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.