Rheem · Heat pump
0 Standby - no call for operation
What the display is showing
The dual seven-segment display on the ICC board shows 0 when line voltage and 24 VAC are present, the thermostat link is communicating and no compressor operation is requested. Normal standby.
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Settings for these units
Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
| Location | Minimum |
|---|---|
| Above unit (fan discharge) | 60 in. [1524 mm] |
| Coil air inlets (3 sides) | 6 in. [152 mm] |
| Service access side | 24 in. [610 mm] |
| Between two units (grille sides aligned) | 12 in. total (6 in. per unit) |
Do not reduce the 60 in. discharge or 24 in. service clearances.
Inlet clearances under 6 in. reduce capacity and efficiency.
Models that show this code
4 models in Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Other codes on the same units
- 01 Long run time (compressor)
- 1 flash (L terminal) L-terminal fault output: Long run cycle or low pressure
- 02 High side fault (compressor limit opened 4 times)
- 2 flashes (L terminal) L-terminal fault output: High pressure control trip
- 03 Short cycling
- 3 flashes (L terminal) L-terminal fault output: Unit short cycling
- 4 flashes (L terminal) L-terminal fault output: Locked rotor
- 05 Open circuit - compressor will not run
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.3 and 12.6 ICC diagnostic codes, pp.19 and 25. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.