Glow Brand boiler error codes

62 codes (53 faults, 9 normal display and menu codes), plus 1 settings tables.

CodeMeaningSeverity / type
ALEgAnti-legionella runNormal status
AttEWarning prefixMenu / mode display
AttE 202Unknown appliance model selectedLow
AttE 204Outdoor sensor open or shortedLow
CodEInstaller password promptMenu / mode display
ErrBlocking error prefixMenu / mode display
Err 100Internal software error (blocking)Medium
Err 101Internal software error (blocking)Medium
Err 102Internal software error (blocking)Medium
Err 103Internal software error (blocking)Medium
Err 104Internal software error (blocking)Medium
Err 105CH supply over 180 F (82 C)Medium
Err 106Internal software error (blocking)Medium
Err 107Internal software error (blocking)Medium
Err 108Internal software error (blocking)Medium
Err 109Internal software error (blocking)Medium
Err 110Internal software error (blocking)Medium
Err 111Internal software error (blocking)Medium
Err 112Internal software error (blocking)Medium
Err 113Internal software error (blocking)Medium
Err 114False flame detectedMedium
Err 116Low water pressure (FILL)Medium
Err 119CH return temperature sensor openMedium
Err 120CH supply temperature sensor openMedium
Err 122DHW tank temperature sensor openMedium
Err 123Flue temperature sensor openMedium
Err 126CH return temperature sensor shortedMedium
Err 127CH supply temperature sensor shortedMedium
Err 129DHW tank temperature sensor shortedMedium
Err 130Flue temperature sensor shortedMedium
Err 134Too many resets in a short timeLow
Err 156Blocked flue switch openMedium
Err 162Low water pressure under 10 psi (FILL)Medium
FILLLow water pressure promptNormal status
LocLockout prefixMenu / mode display
Loc 0Internal software faultHigh
Loc 1Ignition failed three times in a rowHigh
Loc 10Wrong safety parameters in EEPROMHigh
Loc 11Internal software faultHigh
Loc 12Internal software faultHigh
Loc 15High limit exceeded (203 F / 95 C)High
Loc 16Flue temperature too highHigh
Loc 17Internal software faultHigh
Loc 18Internal software faultHigh
Loc 19Internal software faultHigh
Loc 2Gas valve relay faultHigh
Loc 20Flame still present 10 s after gas valve closedHigh
Loc 21Flame detected before ignitionHigh
Loc 22Three flame failures in one demandHigh
Loc 23Error code memory corruptedHigh
Loc 3Safety relay faultHigh
Loc 33Low water cut-off circuit openHigh
Loc 38Blocked flue switch tripped more than 3 times in 24 hHigh
Loc 4Blocking error lasted over 20 hoursMedium
Loc 5Fan not running for more than 60 secondsHigh
Loc 6Fan running too slow for more than 60 secondsHigh
Loc 7Fan running too fast for more than 60 secondsHigh
Loc 8Internal software faultHigh
Loc 9EEPROM contents out of dateHigh
dAirDe-air sequence runningNormal status
initDisplay starting upNormal status
tEStSystem test activeNormal status

Settings and specs

Maintenance intervals

Maintenance · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)
  • Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 14.1-14.2 p.69

Models covered

B120B160B85

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.