Glow Brand · Boiler
Loc 23 Error code memory corrupted
What the control is telling you
The stored error code byte in RAM was corrupted to an unknown value.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Control memory fault
Test and repair steps
- Press RESET on the display, then the small reset button on the back of the ignition control board (ICB).
- If the same code keeps coming back, replace the ICB and the display board together.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Loc 2 Gas valve relay fault
- Loc 20 Flame still present 10 s after gas valve closed
- Loc 21 Flame detected before ignition
- Loc 22 Three flame failures in one demand
- Loc 3 Safety relay fault
- Loc 33 Low water cut-off circuit open
- Loc 38 Blocked flue switch tripped more than 3 times in 24 h
- Loc 4 Blocking error lasted over 20 hours
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.