Glow Brand · Boiler

Loc 4 Blocking error lasted over 20 hours

Medium severity Glow B85/B120/B160

What the control is telling you

A blocking error (Err) stayed active for 20 hours straight, so the control turned it into a lockout. Parameter 1.052 shows which blocking error it was.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Any blocking error left unresolved for 20 hours

Test and repair steps

  1. Read parameter 1.052 to find the last blocking error and fix that cause first.
  2. Press RESET on the display and on the back of the ICB.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Other codes on the same units

  • Loc 23 Error code memory corrupted
  • Loc 3 Safety relay fault
  • Loc 33 Low water cut-off circuit open
  • Loc 38 Blocked flue switch tripped more than 3 times in 24 h
  • Loc 5 Fan not running for more than 60 seconds
  • Loc 6 Fan running too slow for more than 60 seconds
  • Loc 7 Fan running too fast for more than 60 seconds
  • Loc 8 Internal software fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.