Glow Brand · Boiler

Loc 7 Fan running too fast for more than 60 seconds

High severity Glow B85/B120/B160

What the control is telling you

Fan speed stayed above target for over a minute.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Loose or poor line, neutral or ground connection to the boiler, or a bad internal ground
  • Loose fan wiring at the fan or ICB
  • Damaged harness
  • Failed fan

Test and repair steps

  1. Check line, neutral and ground and the internal grounds.
  2. Check fan wiring at both ends.
  3. Replace the harness.
  4. Replace the fan.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Other codes on the same units

  • Loc 38 Blocked flue switch tripped more than 3 times in 24 h
  • Loc 4 Blocking error lasted over 20 hours
  • Loc 5 Fan not running for more than 60 seconds
  • Loc 6 Fan running too slow for more than 60 seconds
  • Loc 8 Internal software fault
  • Loc 9 EEPROM contents out of date
  • dAir De-air sequence running
  • init Display starting up

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.