Glow Brand · Boiler · Ignition

Ignition and retry

B85/B120/B160

What happens, in order

  1. Heat demand starts the combustion fan; a brief fan purge runs first
  2. Ignition control opens the gas valve and sparks; flame is proven with the flame sensor
  3. If flame is not proven the control retries ignition 2 more times (3 attempts total)
  4. Three failed attempts give lockout Loc 1 (ignition error)
  5. Loc 1 and Loc 2 are hard lockouts; cycling power does not clear them, hold RESET on the display to clear
  6. If flame is lost during normal running the boiler locks out on flame failure

Timings and thresholds

ItemValue
Ignition attempts3 total (1 + 2 retries)
Fan fault lockout (Loc 5/6/7)fan speed wrong for more than 60 s

Codes you may see during this

Loc 1 Loc 2 Loc 3 Loc 5 Loc 6 Loc 7 Err 114

Applies to: B85, B120, B160

Models

B85B120B160

More Glow Brand boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Glow Brand B85/B120/B160 Installation and Operating Manual (sections 10.2, 11.7, 11.8, 11.10, 12.1). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.