Glow Brand · Boiler
Err 114 False flame detected
What the control is telling you
A flame signal is present when there should be none.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Flame still burning after the demand ends
- Faulty ionization sensor or cable
- Faulty ignition electrode or cable
- Blocked condensate drain
- Failed ICB
Test and repair steps
- Look through the observation window on the heat exchanger: there should be no flame once the demand is satisfied.
- Check or replace the ionization sensor and its cable.
- Check or replace the ignition electrode and its cable.
- Clear the condensate drain.
- Replace the ICB if the error remains.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Err 110 Internal software error (blocking)
- Err 111 Internal software error (blocking)
- Err 112 Internal software error (blocking)
- Err 113 Internal software error (blocking)
- Err 116 Low water pressure (FILL)
- Err 119 CH return temperature sensor open
- Err 120 CH supply temperature sensor open
- Err 122 DHW tank temperature sensor open
Sequence of operation
What the unit does around this code, step by step.
- Ignition and retry · Ignition
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.2 p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.