Glow Brand · Boiler
Err 122 DHW tank temperature sensor open
What the control is telling you
The control reads the dhw tank temperature sensor as open (10 kohm NTC).
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Sensor open
- Sensor wiring or connector
- Wrong DHW mode setting (DHW sensor only)
Test and repair steps
- If no tank sensor is used, set DHW Mode (2.035) to 0.
- If DHW Mode 1 is used, check the sensor is wired to terminals 5 and 6.
- Measure the sensor it should read about 10,000 ohm at 77 F (25 C); use the resistance table for other temperatures.
- If the resistance is right, check the wiring between sensor and control.
- Replace the sensor.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Err 114 False flame detected
- Err 116 Low water pressure (FILL)
- Err 119 CH return temperature sensor open
- Err 120 CH supply temperature sensor open
- Err 123 Flue temperature sensor open
- Err 126 CH return temperature sensor shorted
- Err 127 CH supply temperature sensor shorted
- Err 129 DHW tank temperature sensor shorted
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.2 p.65. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.