Glow Brand · Boiler
Err 116 Low water pressure (FILL)
What the control is telling you
Water pressure fell below the minimum (4 psi / 0.3 bar). The display also shows FILL and the burner is blocked.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- System not filled or leaking
- Expansion tank precharge wrong
- Dirty or failed pressure sensor
- Pressure sensor wiring
Test and repair steps
- Raise system pressure to at least 16 psi (1.1 bar), then cycle power.
- If the external gauge reads over 20 psi while the error is still on, inspect the pressure sensor and its harness; clean a dirty sensor gently with a calcium/rust remover.
- Replace the pressure sensor if it still misreads.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Err 111 Internal software error (blocking)
- Err 112 Internal software error (blocking)
- Err 113 Internal software error (blocking)
- Err 114 False flame detected
- Err 119 CH return temperature sensor open
- Err 120 CH supply temperature sensor open
- Err 122 DHW tank temperature sensor open
- Err 123 Flue temperature sensor open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.2 p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.