Glow Brand · Boiler · Freeze protection

Anti-frost pre-heat

B85/B120/B160

What happens, in order

  1. Boiler needs power and gas; frost protection icon flashes when active (default mode 1)
  2. If supply, return or flue temperature falls to 50 F (10 C) the CH pump starts
  3. If temperature keeps dropping by a further 9 F (5 C) the burner fires at minimum power
  4. Burner runs until the return temperature reaches 59 F (15 C)

Timings and thresholds

ItemValue
Pump starts50 F (10 C)
Burner firesa further 9 F (5 C) drop
Burner stopsreturn 59 F (15 C)

Applies to: B85, B120, B160

Models

B85B120B160

More Glow Brand boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Glow Brand B85/B120/B160 Installation and Operating Manual (sections 10.2, 11.7, 11.8, 11.10, 12.1). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.