Glow Brand · Boiler · Heating

Central heat call and post purge

B85/B120/B160

What happens, in order

  1. Demand comes from thermostat or end switch on terminals 9 and 10 (mode 0), or from the outdoor sensor (mode 2), per CH mode parameter 2.001
  2. Outdoor reset modes (1, 2) calculate the setpoint between design supply 2.019 and baseline supply 2.021 using outdoor temperature
  3. Mode 2 runs a permanent demand while outdoor temperature is below warm weather shutdown (2.025)
  4. Boiler fires and modulates to reach the CH setpoint (2.003)
  5. When demand ends the burner stops and the fan post purges
  6. After post purge the primary and CH pumps keep running for the CH post circulation period (2.005)

Timings and thresholds

ItemValue
CH setpointparameter 2.003
CH post circulationparameter 2.005
Warm weather shutdownparameter 2.025, default 72 F

Applies to: B85, B120, B160

Models

B85B120B160

More Glow Brand boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Glow Brand B85/B120/B160 Installation and Operating Manual (sections 10.2, 11.7, 11.8, 11.10, 12.1). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.